Publication 1769-UM002B-EN-P - July 2005

Configuring Modules in a Remote DeviceNet System with a 1769-ADN DeviceNet Adapter D-5

4. Double-click this slot 1 box.

By default, the 1769-IF4 module contains six input words and no output
words.

5. Click the Data Description button to see what the six input words

represent.

The first four words are the actual analog input data, while the last two
words contain status and over- and under-range bits for the four
channels.

6. Click OK or Cancel to exit this screen and return to the Configuration

screen.

7. If your application requires only four data words and not the status

information, click the Set for I/O only button

The input size changes to four words. The revision number for the
series B 1769-IF4 module is two. With this setting, you may leave the
electronic keying to Exact Match. It is not recommended to disable
keying, but if you are not sure of the exact revision of your module,
selecting Compatible Module allows your system to operate, while still
requiring a 1769-IF4 module in slot 1.

The series B 1769-IF4 module differs from the series A module only in
that it allows external 24V dc power. The external power connection
allows you to draw 24V dc power for the module from your external
source, should your 1769 power supply not provide enough 24V dc
power for your particular set of 1769 I/O modules.