Configuring MicroLogix 1100/1200/1500 Controllers 3-61
String Length of Record
The size of a record is limited so that the length of the maximum
formatted string does not exceed 80 characters. The following table
can be used to determine the formatted string length.
For queue 5, the formatted string length is 29 characters, as shown
below:
= 8 + 1 + 6 + 1 + 6 + 1 + 6 = 29 characters
Number of Records
Using Queue 5 as an example, each record consumes:
Each record consumes 10 bytes. So if only one queue was configured,
the maximum number of records that could be stored would be 4915.
The maximum number of records is calculated by:
Maximum Number of Records = Data Log File Size/Record Size
= 48K bytes/10 bytes
= (48)(1024)/10
= 4915 records
Data
Memory Consumed
Formatted String Size
delimiter
0 bytes
1 character
word
2 bytes
6 characters
long word
4 bytes
11 characters
date
2 bytes
10 characters
time
2 bytes
8 characters
Data
Time
N7:11
I1:3.0
I1:2.1
Characters
8
1
6
1
6
1
6
Record Field
Memory Consumption
Time
2 bytes
N7:11
2 bytes
I1:3.0
2 bytes
I1:2.1
2 bytes
Integrity Check
2 bytes
Total
10 bytes