Mds model 2310 and 4310 remote stations -37, Cable pin assignments – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual
Page 303

Publication AG-UM008C-EN-P - February 2005
Configuring Modems 8-37
MDS Model 2310 and 4310 Remote Stations
Models 2310 and 4310 are multiple address, remote data transceiver
stations.
Cable Pin Assignments
Each of these models requires a 25-pin male connector with the
following pin assignments:
Figure 8.23 MDS Model 2310 and Model 4310 Remote Data Transceivers
DC IN
+
-
ANTENNA
DIAG
PWR SYNC TXD RXD
RS-232 data port
SLC 5/03
Female DB 25-pin
connector
Male DB 25-pin
connector
RS-232 data port
Table 8.31 MSD Model 2310 and 4310 Pin Assignments
Modem
25-pin
female
Pin Name
Pin Name
PLC-5
25-pin
female
SLC
9-pin male
1
Protective GND
—
Shield
1
CASE
2
TXD.IN
—
TXD.OUT
2
3
3
RXD.OUT
—
RXD.IN
3
2
4
RTS.IN
—
RTS.OUT
4
7
5
CTS.OUT
—
CTS.IN
5
8
6
DSR.OUT
(1)
(1) DSR.OUT provides a +8V DC DSR signal through a 1K-ohm resistor.
—
DSR.IN
6
6
7
SIG.GND
—
SIG.GND
7
5
8
DCD.OUT
—
DCD.IN
8
1