Configuring Modems 8-15
Cable Pin Assignments
The Model 137-001 requires a 15-pin male connector with the pin
assignments shown below or these MARC cable assemblies:
•
127-056 (1785-KE to MARC 137-001)
•
127-067 (1785 PLC-5/xx to MARC 137-001)
Figure 8.9 MARC, Inc. Model 137-001
Table 8.12 MARC, Inc. Model 137-001 Pin Assignments
Switch Settings
For Bell 202 full-duplex operating mode, set the switches on Model
137-001 according to those in Table 8.13. For Bell 202 half-duplex
mode (point-to-multipoint), set the switches on Model 166-101
according to those in Table 8.14.
MARC
15-pin D female
port
RJ11 jack
5 Receive(-)
4 Transmit (-)
3 Transmit (+)
2 Receive (+)
To Allen-Bradley PLC-5/xx
or 1785-KE
Modem
15-pin female
Pin Name
Pin Name
PLC-5
25-pin female
1785-KE
15-pin female
1
DCD.OUT
—
DCD.IN
8
8
2
TXD.IN
—
TXD.OUT
2
2
3
RXD.OUT
—
RXD.IN
3
3
4
DTR.IN
—
DTR.OUT
20
(2)
(2) Pin 6 is jumpered (within the connector) to pin 20.
11
(3)
(3) Pin 6 is jumpered (within the connector) to pin 11.
5
(1)
(1) Pin 5 is jumpered (within the connector) to pin 9.
SIG.GND
—
SIG.GND
7
7
(4)
(4) Pin 7 is jumpered (within the connector) to pin 13.
7
RTS.IN
—
RTS.OUT
4
4
8
CTS.OUT
—
CTS.IN
5
5