Caution – Carrier 48TC*D08 User Manual

Page 7

Advertising
background image

7

Routine Cleaning of NOVATION Condenser Coil

Surfaces
To clean the NOVATION condenser coil, chemicals are

NOT to be used; only water is approved as the cleaning

solution. Only clean potable water is authorized for

cleaning NOVATION condensers. Carefully remove any

foreign objects or debris attached to the coil face or

trapped within the mounting frame and brackets. Using a

high pressure water sprayer, purge any soap or industial

cleaners from hose and/or dilution tank prior to wetting

the coil.

Clean condenser face by spraying the coil core steadily

and uniformly from top to bottom, directing the spray

straight into or toward the coil face. Do not exceed 900

psig or a 45 degree angle; nozzle must be at least 12 in.

(30 cm) from the coil face. Reduce pressure and use

caution to prevent damage to air centers (fins). Do not

fracture the braze between air centers and refrigerant

tubes. Allow water to drain from the coil core and check

for refrigerant leaks prior to start--up.
NOTE: Please see the NOVATION Condenser Service
section for specific information on the coil.

PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal

injury or equipment damage.
Chemical cleaning should NOT be used on the

aluminum NOVATION condenser. Damage to the coil

may occur. Only approved cleaning is recommended.

CAUTION

!

Routine Cleaning of Evaporator Coil Sufaces
Monthly cleaning with Totaline® environmentally sound

coil cleaner is essential to extend the life of coils. This

cleaner is available from Carrier Replacement parts

division as part number P902--0301 for one gallon

container, and part number P902--0305 for a 5 gallon

container. It is recommended that all round tube coil

cleaner as described below. Coil cleaning should be part

of the unit’s regularly scheduled maintenance procedures

to ensure long life of the coil. Failure to clean the coils

may result in reduced durability in the environment.

Avoid the use of

S

coil brighteners

S

acid cleaning prior to painting

S

high pressure washers

S

poor quality water for cleaning

Totaline

environmentally

sound

coil

cleaner

is

non--flammable, hypoallergenic, non--bacterial, and a

USDA accepted biodegradable agent that will not harm

coil or surrounding components such as electrical wiring,

painted

metal

surfaces,

or

insulation.

Use

of

non--recommended coil cleaners is strongly discouraged

since coil and unit durability could be affected.

Totaline Environmentally Sound Coil Cleaner Application

Equipment

S

2-1/2 gallon garden sprayer

S

water rinse with low velocity spray nozzle

PERSONAL INJURY HAZARD
Failure to follow this caution may result in corrosion

and damage to the unit.
Harsh chemicals, household bleach or acid or basic

cleaners should not be used to clean outdoor or indoor

coils of any kind. These cleaners can be very difficult

to rinse out of the coil and can accelerate corrosion at

the fin/tube interface where dissimilar materials are in

contact. If there is dirt below the surface of the coil,

use the Totaline environmentally sound coil cleaner as

described above.

CAUTION

!

PERSONAL INJURY HAZARD
Failure to follow this caution may result in reduced

unit performance.
High velocity water from a pressure washer, garden

hose, or compressed air should never be used to clean

a coil. The force of the wter or air jet will bend the fin

edges and icrease airside pressure drop.

CAUTION

!

Totaline Environmentally Sound Coil Cleaner application

Instructions

1. Proper eye protection such as safety glasses is recom-

mended during mixing and application.

2. Remove all surface loaded fibers and dirt with a vacu-

um cleaner as described above.

3. Thoroughly wet finned surfaces with clean water and

a low velocity garden hose, being carefull not to bend

fins.

4. Mix Totaline environmentally sound coil cleaner in a

2 1/2 gallon garden spryer according to the instruc-

tions included with the cleaner. The optimum solution

temperature is 100°F (38°C).

NOTE: Do NOT USE water in excess of 130°F (54°C),

as the enzymatic activity will be destroyed.

1. Thoroughly apply Totaline® environmentally sound

coil cleaner solution to all coil surfaces including

finned area, tube sheets and coil headers.

2. Hold garden sprayer nozzle close to finned areas and

apply cleaner with a vertical, up--and--down motion.

Avoid spraying in horizontal pattern to minimize po-

tential for fin damage.

3. Ensure cleaner thoroughly penetrates deep into finned

areas.

4. Interior and exterior finned areas must be thoroughly

cleaned.