Carrier 48TC*D08 User Manual

Page 79

Advertising
background image

79

Table 30 – Available Cooling Stages

NUMBER OF

STAGES

0

1

(ECONOMIZER*)

2

3

Compressor 1

Off

Off

On

On

Compressor 2

Off

Off

Off

On

* If conditions are suitable for economizer operation.

Any time the compressors are running, the PremierLink

controller will lockout the compressors if the SAT

becomes too low. These user configurable settings are

found in the SERVICE configuration table:

Compressor 1 Lockout at SAT < SATLO1 (50 to 65_F)

(default is 55_F)

Compressor 2 Lockout at SAT < SATLO2 (45 to 55_F)

(default is 50_F)

After a compressor is locked out, it may be started again

after a normal time--guard period and the supply air

temperature has increased at least 8_F above the lockout

setpoint.

Dehumidification — The PremierLink controller will

provide occupied and unoccupied dehumidification

control when AUXOUT = 5 in the CONFIG table and is

installed on HVAC units that are equipped with additional

controls and accessories to accomplish this function. This

function also requires a space relative humidity sensor be

installed on the OAQ/IRH input.

When in the occupied mode and the indoor relative

humidity is greater then the Occupied High Humidity

setpoint, then the H3_EX_RV output point will be

energized. When in the unoccupied mode and indoor

relative humidity is greater then the Unoccupied High

Humidity setpoint, then the H3_EX_RV output point and

supply fan output will be energized. There is a fixed 5%

hysteresis that the indoor relative humidity must drop

below the active setpoint to end the dehumidification

mode and deenergize the H3_EX_RV output. If the

PremierLink controller is in the unoccupied mode, then

the fan relay will deenergize if there is no other mode

requiring to the fan to be on. This function will not

energize mechanical cooling as a result of the indoor

relative humidity exceeding either setpoint.

A high humidity alarm will be generated if the indoor

relative humidity exceeds the high humidity setpoint by

the amount configured in the Control Humidity Hysteresis

in the ALARMS table for 20 minutes. The alarm will

return to normal when the indoor relative humidity drops

3% below the active humidity setpoint.

Economizer — The economizer dampers are used to

provide free cooling and indoor air quality if optional CO

2

sensor is installed and when the outside conditions are

suitable. Temperature control is accomplished by

controlling the SAT to a certain level determined by the

Economizer PID Loop by calculating a submaster

reference (ECONSR) value. This algorithm will calculate

the submaster reference temperature (ECONSR) based on

OAT and enthalpy conditions and cooling requirements.

The ECONSR value is then passed to the Economizer

Submaster Loop, which will modulate dampers to

maintain SAT at ECONSR level.

The following conditions are required to determine if

economizer cooling is possible:

S

Indoor fan has been on for at least 30 seconds

S

Enthalpy is low

S

SAT reading is available

S

OAT reading is available

S

SPT reading is available

S

OAT ≤ SPT

S

OAT < OATMAX (OATMAX default is 75_F)

S

Economizer position is NOT forced

If any of the above conditions are not met, the ECONSR

will be set to its MAX limit of 120_F and the damper will

go to its configured minimum position. The minimum

damper position can be overridden by the IAQ routine

described later in this section.

The calculation for ECONSR is as follows:

ECONSR = PID function on (setpoint -- SPT), where:
setpoint = ((OCSP+STO) + (OHSP+STO))/2 when

NTLO (Unoccupied Free Cool OAT Lockout) < OAT <

68_F
setpoint = (OCSP+STO) -- 1 when OAT ≤ NTLO
setpoint = (OHSP+STO) + 1 when OAT ≥ 68_F

The actual damper position (ECONPOS) is the result of

the following calculation. Values represented in the right

side of the equation can be found in the SERVICE

configuration table descriptions in this manual. Note that

that the OAT is taken into consideration to avoid large

changes in damper position when the OAT is cold:

ECONPOS = SubGain x (ECONSR--SAT) + CTRVAL
where SubGain = (OAT -- TEMPBAND) / (ESG + 1)

If the OAT < DXLOCK (DX Cool Lockout setpoint) then

the damper will be modulated to maintain the SAT at the

ECONSR value.

48TC