Table 12 — 48HJ005 Fan Performance — Vertical Discharge Units With Standard Motor

Table 13 — 48HJ005 Fan Performance — Vertical Discharge Units With High-Static Motor

LEGEND AND NOTES FOR TABLES 12 AND 13

LEGEND

NOTES:

1. Boldface indicates field-supplied drive required. (See Note 3.)

2.

indicates field-supplied motor and drive required.

3. Motor drive range is 840 to 1185 rpm for standard motor; 1075 to

1455 rpm for high-static motor. All other rpms require a field-supplied
drive.

4. Values include losses for filters, unit casing, and wet coils. See page 28

for accessory/FIOP static pressure information.

5. Maximum continuous bhp is 1.2 for standard motor, 2.4 for high-static

motor. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using your
fan motors up to the ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See Evapora-
tor-Fan Motor Data tables on page 20 for additional information.

6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier

representative to verify.

7. Interpolation is permissible. Do not extrapolate.

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.1

0.2

0.3

0.4

0.6

0.7

0.8

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1200

596

0.20

665

0.25

722

0.31

779

0.36

872

0.48

915

0.54

957

0.60

1300

633

0.24

699

0.30

754

0.36

809

0.42

902

0.55

943

0.61

984

0.67

1400

672

0.30

735

0.36

788

0.42

840

0.48

933

0.62

972

0.69

1011

0.75

1500

711

0.35

770

0.42

822

0.49

873

0.55

963

0.69

1002

0.77

1041

0.84

1600

751

0.42

835

0.49

871

0.56

907

0.63

993

0.77

1033

0.85

1072

0.93

1700

791

0.49

873

0.57

907

0.65

941

0.72

1024

0.87

1064

0.96

1103

1.04

1800

831

0.58

881

0.66

929

0.74

976

0.81

1057

0.97

1095

1.06

1132

1.14

1900

872

0.67

919

0.75

965

0.84

1011

0.92

1091

1.08

1127

1.17

1162

1.25

2000

913

0.77

958

0.86

1002

0.95

1046

1.03

1125

1.21

1160

1.30

1195

1.38

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.9

1.0

1.1

1.2

1.4

1.6

1.8

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1200

993

0.65

1028

0.69

1056

0.72

1083

0.74

1134

0.80

1185

0.88

1331

0.99

1300

1021

0.74

1058

0.80

1090

0.85

1121

0.89

1171

0.94

1219

1.00

1268

1.10

1400

1049

0.82

1086

0.89

1120

0.96

1153

1.00

1210

1.12

1257

1.17

1307

1.25

1500

1077

0.92

1113

0.99

1147

1.06

1180

1.13

1241

1.27

1295

1.37

1339

1.43

1600

1107

1.00

1141

1.09

1174

1.17

1207

1.25

1269

1.40

1326

1.54

1376

1.65

1700

1137

1.12

1171

1.20

1203

1.29

1235

1.37

1296

1.53

1354

1.70

1407

1.84

1800

1167

1.23

1202

1.32

1233

1.41

1263

1.49

1323

1.67

1381

1.85

1436

2.02

1900

1197

1.35

1232

1.45

1263

1.54

1294

1.63

1351

1.81

1408

2.00

1463

2.19

2000

1229

1.48

1262

1.58

1294

1.68

1325

1.78

1362

1.97

1436

2.16

1489

2.36

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1200

665

0.25

779

0.36

872

0.48

957

0.60

1028

0.69

1300

699

0.30

809

0.42

902

0.55

984

0.67

1058

0.80

1400

735

0.36

840

0.48

933

0.62

1011

0.75

1086

0.89

1500

770

0.42

873

0.55

963

0.69

1041

0.84

1113

0.99

1600

835

0.49

907

0.63

993

0.77

1072

0.93

1141

1.09

1700

873

0.57

941

0.72

1024

0.87

1103

1.04

1171

1.20

1800

881

0.66

976

0.81

1057

0.97

1132

1.14

1202

1.32

1900

919

0.75

1011

0.92

1091

1.08

1162

1.25

1232

1.45

2000

958

0.86

1046

1.03

1125

1.21

1195

1.38

1262

1.58

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

1200

1083

0.74

1134

0.80

1185

0.88

1331

0.99

1374

1.09

1300

1121

0.89

1171

0.94

1219

1.00

1268

1.10

1309

1.21

1400

1153

1.00

1210

1.12

1257

1.17

1307

1.25

1349

1.37

1500

1180

1.13

1241

1.27

1295

1.37

1339

1.43

1382

1.57

1600

1207

1.25

1269

1.40

1326

1.54

1376

1.65

1420

1.81

1700

1235

1.37

1296

1.53

1354

1.70

1407

1.84

1452

2.02

1800

1263

1.49

1323

1.67

1381

1.85

1436

2.02

1482

2.22

1900

1294

1.63

1351

1.81

1408

2.00

1463

2.19

2000

1325

1.78

1362

1.97

1436

2.16

1489

2.36

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option