Table 33 — EconoMi$er Flash Code Identification

Table 34 — EconoMi$er Troubleshooting

LEGEND

FLASH CODE

CAUSE

ACTION TAKEN BY ECONOMI$ER

Constant On

Normal operation

Normal operation.

Constant Off

No power

No operation.

Continuous
Flash

CONFIG button pushed and held
between 3 and 9 seconds

Outdoor air damper is stroked fully open, then closed
(automatic test procedure takes 3 minutes to complete).

C

rit

ic

a

l F

a

u

lt

Flash One

Control board fault

System shutdown.

Flash Two

Thermostat fault (i.e., Y2 without Y1)

System shutdown until corrected.

Flash Three

Actuator fault

Revert to mechanical cooling only.

Flash Four

Supply air temperature sensor fault

Continue operation with damper at minimum position.
Revert to mechanical cooling only.

Flash Five

Outdoor air temperature sensor fault

Continue operation with damper at minimum position.
Disable mechanical cooling lockout.

Non

-C

rit

ic

a

l F

a

ul

t

Flash Six

Outdoor air humidity sensor fault

Continue operation with dry bulb or dry bulb differential switchover.

Flash Seven

Return air temperature sensor fault

Continue operation with single enthalpy EconoMi$er
switchover or dry bulb EconoMi$er switchover (without
humidity sensor).

Flash Eight

Return air humidity sensor fault

Continue operation with single enthalpy, differential dry
bulb, or dry bulb EconoMi$er switchover.

Flash Nine

Carbon Dioxide (CO

2

) sensor fault

Continue operation without ventilation control.

Flash Ten

Onboard adjustment potentiometer fault

Continue operation with default potentiometer settings.

PROBLEM

POTENTIAL CAUSE

REMEDY

Damper Does Not
Open

Indoor (Evaporator) Fan is
Off

Check to ensure that 24 vac is present at Terminal C1 (Common Power)
on the IFC (Indoor Evaporator Fan Contactor) or that 24 vac is present at
the IFO (Indoor Evaporator Fan On) terminal. Check whether 24 vac is
present at PL 6-1 (red wire) and/or PL6-3 (black wire). If 24 vac is
not present, check wiring (see unit label diagram).

Check proper thermostat connection to G on the connection board.

No Power to EconoMi$er
Controller

Check to ensure that 24 vac is present across Terminals 24 VAC and
24 V COM on the EconoMi$er control. If 24 vac is not present, check wiring
(see unit label diagram). If 24 vac is present, STATUS light should be on
constantly.

No Power to G Terminal

If IFM is on, check to ensure 24 vac is present on G Terminal of the
EconoMi$er controller. If 24 vac is not present, check wiring (see unit
label diagram).

Controller Fault

If STATUS light is flashing one flash, the EconoMi$er controller is
experiencing a fault condition. Cycle power to the controller. If condition
continues, replace the EconoMi$er controller.

Thermostat Fault

If STATUS light is flashing two flashes, the EconoMi$er controller senses
the thermostat is wired incorrectly. Check wiring between the thermostat
and the connection board in the electrical panel. The fault condition is
caused by Y2 being energized before Y1.

Actuator Fault

Check the wiring between the EconoMi$er controller and the actuator.

Hold CONFIG button between 3 and 10 seconds to verify the
actuator’s operation. (This process takes 3 minutes to complete.)

EconoMi$er
Operation Limited to
Minimum Position

Minimum Position Set
Incorrectly

Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%)
to 100% to verify operation, and then set to correct setting.

EconoMi$er Changeover
Set Point Set Too High or
Too Low

Set at correct value. See Table 3.

Supply Air Temperature
Sensor Faulty

If STATUS light is flashing 4 flashes, Supply Air Temperature Sensor is
faulty. Check wiring or replace sensor.

Outdoor Air Temperature
Sensor Faulty

If STATUS light is flashing 5 flashes, Outdoor Air Temperature Sensor is
faulty. Check wiring or replace sensor.

Damper Position
Less than Minimum
Position Set Point

Supply Air Low Limit
Strategy Controlling

The supply-air temperature is less than 45 F, causing the minimum
position to be decreased. Refer to the Start-Up instructions. Verify correct
setting of MIN POS (%). If correct, EconoMi$er is operating correctly.

Damper Does Not
Return to Minimum
Position

CO

2

Ventilation Strategy

Controlling

If a CO

2

sensor is being used, and the damper position is greater than

minimum position, the ventilation control strategy is controlling. Refer to
the Start-Up instructions. EconoMi$er is operating correctly.

Damper Does Not
Close on Power Loss

Damper Travel is
Restricted

Check to ensure the damper is not blocked.

IFM

Indoor Fan Motor

PL

Plug