Carrier 50HE003-006 User Manual

Page 63

Advertising
background image

63

Table 35—Humidi-Mizer Adaptive Dehumidification System Sequence of Operation and

System Response — Single Compressor Unit (50HE003--006, 50HJ004-007)

THERMOSTAT INPUT

ECONOMIZER FUNCTION

48HE, HJ UNIT OPERATION

H

Y1

Y2

OAT. < Economizer Set Point

Economizer

Comp. 1

Subcooling Mode

Hot Gas Reheat Mode

Off

Normal Operation

On

On

On

No

Off

On

Yes

No

On

On

Off

No

Off

On

Yes

No

On

On

On

Yes

On

On

Yes

No

On

On

Off

Yes

On

On

No

Yes

On

Off

Off

No

Off

On

No

Yes

NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.

LEGEND

OAT --- Outdoor Air Temperature

C06046

Fig. 56

--- Separating Coil Sections

4. Remove device holding coil sections together at return end

of condenser coil. Carefully separate the outer coil section
3 to 4 in. from the inner coil section. (See Fig. 57.)

5. Use a water hose or other suitable equipment to flush

down between the 2 coil sections to remove dirt and

debris. Clean the outer surfaces with a stiff brush in the
normal manner.

6. Secure the sections together. Reposition the outer coil

section and remove the coil corner post from between the
top panel and center post. Install the coil corner and center

posts. Replace all screws.

Condensate Drain
Check and clean each year at the start of the cooling season. In

winter, keep the drain dry or protect it against freeze-up.
Filters
Clean or replace at the start of each heating and cooling season, or
more often if operating conditions require it. Replacement filters

must be the same dimensions as the original filters.
Outdoor--Air Inlet Screen
Clean the screen with steam or hot water and a mild detergent. Do

not use disposable filters in place of screens.
Step 2

—Lubrication

Compressor
The compressor is charged with the correct amount of oil at the
factory.

Fan Motor Bearings
Fan motor bearings are permanently lubricated. No further

lubrication is required.

No lubrication of condenser-fan or

evaporator-fan motors is required.
Evaporator Fan Belt Adjustment
Inspect evaporator fan belt for wear, proper belt tension, and

pulley alignment as conditions require or at the beginning of each
heating and air conditioning season. Refer to Step 7 -- Adjust

Evaporator Fan Speed for adjustment and alignment procedures.
Step 3

—Condenser--Fan Adjustment

Shut off unit power supply. Remove condenser-fan assembly
(grille, motor, motor cover, and fan) and loosen fan hub

setscrews. Adjust fan height as shown in Fig. 57. Tighten

setscrews and replace condenser-fan assembly.

UNIT

FAN HEIGHT (in.) — “A”

003-006 AND 007 (208/230 v)

2.75

007 (460 v)

3.50

C06138

Fig. 57

--- Condenser--Fan Adjustment

Step 4

—EconoMi$er IV Adjustment

Refer to Optional EconoMi$er IV and EconoMi$er2 section.
Step 5

—Refrigerant Charge

Amount of refrigerant charge is listed on unit nameplate (also
refer to Table 1). Refer to HVAC Servicing Procedures literature

available at your local distributor and the following procedures.
Unit panels must be in place when unit is operating during

charging procedure. Unit must operate a minimum of 10 minutes

before checking or adjusting refrigerant charge.
No Charge
Use standard evacuating techniques. After evacuating system to
500 microns, weigh in the specified amount of refrigerant. (Refer

to Table 1 and unit information plate.)

50H

E,

H

J

Advertising
This manual is related to the following products: