Low Charge Cooling
Using Cooling Charging Charts, Fig. 58--61, vary refrigerant

until the conditions of the charts are met. Note the charging charts
are different from type normally used. Charts are based on

charging the units to the correct superheat for the various
operating conditions. Accurate pressure gage and temperature

sensing device are required. Connect the pressure gauge to the

service port on the suction line. Mount the temperature sensing
device on the suction line and insulate it so that outdoor ambient

temperature does not affect the reading. Indoor-air cfm must be
within the normal operating range of the unit. An accurate

superheat, thermocouple--type or thermistor--type thermometer,

and a gauge manifold are required when using the superheat
charging method for evaluating the unit charge. Do not use

mercury or small dial--type thermometers because they are not
adequate for this type of measurement.

C06139

Fig. 58

--- Cooling Charging Chart,

Standard 50HJ004

Humidi--MizerSystem Charging
The system charge for units with the Humidi-MiZer adaptive
dehumidification system is greater than that of the standard unit

alone. The charge for units with this option is indicated on the

unit nameplate drawing. Also refer to Fig. 62-65. To charge

systems using the Humidi-MiZer adaptive dehumidification

system, fully evacuate, recover, and recharge the system to the
nameplate specified charge level. To check or adjust refrigerant

charge on systems using the Humidi-MiZer adaptive

dehumidification system, charge per Fig. 62-65.

C06140

Fig. 59

--- Cooling Charging Chart,

Standard 50HJ005

C06141

Fig. 60

--- Cooling Charging Chart,

Standard 50HJ006

50H

E,

H

J