Test the GFCI receptacle by pressing the TEST button on

the face of the receptacle to trip and open the receptacle.

Check for proper grounding wires and power line phasing

if the GFCI receptacle does not trip as required. Press the

RESET button to clear the tripped condition.

C08283

UNIT

VOLTAGE

CONNECT

AS

PRIMARY

CONNECTIONS

TRANSFORMER

TERMINALS

208,

230

240

L1: RED +YEL

L2: BLU + GRA

H1 + H3

H2 + H4

460

480

L1: RED

Splice BLU + YEL

L2: GRA

H1

H2 + H3

H4

575

600

L1: RED

L2: GRA

H1

H2

Fig. 34 -- Unit Powered Convenience Outlet Wiring

Fuse on power type: The factory fuse is a Bussman

“Fusetron” T--15, non--renewable screw--in (Edison base)

type plug fuse.

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal

injury or death.
Using unit--mounted convenience outlets: Units with

unit--mounded convenience outlet circuits will often

require that two disconnects be opened to de--energize

all power to the unit. Treat all units as electrically

energized until the convenience outlet power is also

checked and de--energization is confirmed. Observe

National Electrical Code Article 210, Branch Circuits,

for use of convenience outlets.

!

WARNING

Installing

Weatherproof

Cover:

A

weatherproof

while-in-use cover for the factory-installed convenience

outlets is now required by UL standards. This cover cannot

be factory-mounted due its depth; it must be installed at unit

installation. For shipment, the convenience outlet is covered

with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control

box. The kit includes the hinged cover, a backing plate and

gasket.

DISCONNECT

ALL

POWER

TO

UNIT

AND

CONVENIENCE OUTLET. LOCK--OUT AND TAG--OUT

ALL POWER.

Remove the blank cover plate at the convenience outlet;

discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until

approximately

1

/

2

-in (13 mm) under screw heads are

exposed. Press the gasket over the screw heads. Slip the

backing plate over the screw heads at the keyhole slots

and align with the gasket; tighten the two screws until

snug (do not over-tighten).

Mount the weatherproof cover to the backing plate as

shown in Fig. 35. Remove two slot fillers in the bottom of

the cover to permit service tool cords to exit the cover.

Check for full closing and latching.

RECEPTACLE
NOT INCLUDED

COVER – WHILE-IN-USE
WEATHERPROOF

BASE PLATE FOR
GFCI RECEPTACLE

C09022

Fig. 35 -- Weatherproof Cover Installation

48TC

**16