Carrier 48TC**16 User Manual

Page 25

Advertising
background image

25

Supply Air Temperature (SAT) Sensor —

On FIOP--equipped 48TC**16 units, the unit is supplied

with a supply--air temperature (SAT) sensor (33ZCSENSAT).

This sensor is a tubular probe type, approx 6--inches (12.7

mm) in length. It is a nominal 10--k ohm thermistor.

The SAT is factory--wired. The SAT probe is wire--tied to

the supply--air opening (on the horizontal opening end) in

its shipping position. Remove the sensor for installation.

Re--position the sensor in the flange of the supply--air

opening or in the supply air duct (as required by local

codes). Drill or punch a

1

/

2

--in. hole in the flange or duct.

Use the template provided in the unit control box. Use two

field--supplied, self--drilling screws to secure the sensor

probe in a horizontal orientation. See Fig. 48.

SUPPLY AIR

RETURN AIR

SUPPLY AIR
TEMPERATURE
SENSOR

ROOF
CURB

C10020

Fig. 48 -- Typical Mounting Location for Supply Air

Temperature (SAT) Sensor on Small Rooftop Units

NOTE:

Refer to Form 33CS--67SI (or latest) for

complete PremierLink configuration, operating sequences

and troubleshooting information. Have a copy of this
manual available at unit set--up

NOTE: The sensor must be mounted in the discharge

airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
Outdoor Air Temperature (OAT) Sensor —

The OAT is factory--mounted in the EconoMi$er2 (FIOP or

accessory). It is a nominal 10k ohm thermistor attached to

an eyelet mounting ring.

EconoMi$er2 —

The PremierLink control is used with EconoMi$er2

(option or accessory) for outdoor air management. The

damper position is controlled directly by the PremierLink

control; EconoMi$er2 has no internal logic device.

Outdoor air management functions can be enhanced with

field--installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors)
Space CO

2

sensor

Outdoor air CO

2

sensor

Refer to Table 3 for accessory part numbers.

Field Connections

Field connections for accessory sensor and input devices

are made at the 16--pole terminal block (TB3) located

beneath the PremierLink control (see Fig. 46). Some input

devices also require a 24--vac signal source; connect at

CTB terminal R at “THERMOSTAT” connection strip for

this signal source. See connections figures on following

pages for field connection locations (and for continued

connections at the PremierLink board inputs). Route wires

to control box as indicated in Fig. 39.

Table 4 provides a summary of field connections for units

equipped with Space Sensor. Table 5 provides a summary of

field connections for units equipped with Space Thermostat.

Table 3 – PremierLink Sensor Usage

APPLICATION

OUTDOOR AIR

TEMPERATURE

SENSOR

RETURN AIR

TEMPERATURE

SENSOR

OUTDOOR AIR

ENTHALPY SENSOR

RETURN AIR

ENTHALPY SENSOR

Differential Dry Bulb

Temperature with

PremierLink

(PremierLink requires

4---20 mA Actuator)

Included ---

CRTEMPSN001A00

Required ---

33ZCT55SPT

or equivalent

---

---

Single Enthalpy with

PremierLink

(PremierLink requires

4---20mA Actuator)

Included ---

Not Used

---

Requires ---

33CSENTHSW

---

Differential Enthalpy

with PremierLink

(PremierLink requires

4---20mA Actuator)

Included ---

Not Used

---

Requires ---

33CSENTHSW

or equivalent

Requires ---

33CSENTSEN

or equivalent

NOTES:

CO

2

Sensors (Optional):

33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPCO2 --- Aspirator box used for duct---mounted CO

2

room sensor.

33ZCT55CO2 --- Space temperature and CO

2

room sensor with override.

33ZCT56CO2 --- Space temperature and CO

2

room sensor with override and setpoint.

48TC

**16