Use a high temperature torch to disconnect the suction line and the discharge line

from the compressor.

d) Remove the mounting bolts and the compressor. Save the mounting hardware

to attach the grommets and sleeves shipped with the replacement compressor.

e) To test for acid and to assure excess oil does not remain in the circuit, remove

oil from the failed compressor. Measure the amount of oil.

CAUTION: In addition to the required eye protection and gloves, care

should be taken in handling POE oil because it may cause damage to
certain plastics and roofing materials. See Hazard Levels, page 2.

If the oil taken from the compressor and measured is found to be significantly

lower than listed in the table below, clean the excess oil through use of suction

and liquid line filter driers. Beginning in Step 4, follow the same procedure as

for burnout cleanup.

Use an acid test kit to check the oil for acid. If acid is found, beginning in

Step

4, follow procedures indicated for burnout cleanup.

Dispose of oil and compressor using an approved environmentally safe

disposal method.

3.7 Compressor

Operation,

Maintenance,

and

Replacement

(cont'd)

Compressor Oil Charge (POE Oil)

Compressor Model

cc

oz

ZP51K5E-TF5

1124

38

ZP51K5E-TFD

1124

38

ZP51K5E-TFE

1124

38

ZP72KCE-TF5

1656

56

ZP72KCE-TFD

1656

56

ZP72KCE-TFE

1656

56

ZP83KCE-TF5

1656

56

ZP83KCE-TFD

1656

56

ZP83KCE-TFE

1656

56

ZP103KCE-TF5

3135

106

ZP103KCE-TFD

3135

106

ZP103KCE-TFE

3135

106

ZP120KCE-TF5

3135

106

ZP120KCE-TFD

3135

106

ZP120KCE-TFE

3135

106

ZP137KCE-TF5

3135

106

ZP137KCE-TFD

3135

106

ZP137KCE-TFE

3135

106

ZP182KCE-TW5

3135

106

ZP182KCE-TWD

3135

106

ZP182KCE-TWE

3135

106

ZPD34K5E-PFV

1124

38

ZPD34K5E-TF5

1124

38

ZPD34K5E-TFD

1124

38

Important NOTES: These

R-410A compressors use a

polyester (POE) lubricant.

Types of recommended POE

oil are Copeland Ultra 22

CC, Copeland Ultra 32 CC,

Copeland Ultra 32-3MAF, Mobil

EAL, Arctic 22 CC, Uniqema

Emkarate RL32CF, or Uniqema

RL32-3MAF.

POE oil absorbs moisture much

quicker and to a greater degree

than standard mineral oil. The

compressor must not be left

open longer than 15 minutes

during replacement. During

installation the system must be

swept with an inert gas such as

dry nitrogen to keep moisture

from entering the compressor

and prevent the formation of

oxides.

Compressor Model

cc

oz

ZPD34K5E-TFE

1124

38

ZPD51K5E-PFV

1124

38

ZPD51K5E-TF5

1124

38

ZPD51K5E-TFD

1124

38

ZPD51K5E-TFE

1124

38

ZPD72KCE-TF5

1774

60

ZPD72KCE-TFD

1774

60

ZPD72KCE-TFE

1774

60

ZPD83KCE-TF5

1656

56

ZPD83KCE-TFD

1656

56

ZPD83KCE-TFE

1656

56

ZPD103KCE-TF5

3135

106

ZPD103KCE-TFD

3135

106

ZPD103KCE-TFE

3135

106

ZPD120KCE-TF5

3135

106

ZPD120KCE-TFD

3135

106

ZPD120KCE-TFE

3135

106

ZPD137KCE-TF5

3135

106

ZPD137KCE-TFD

3135

106

ZPD137KCE-TFE

3135

106

ZPD182KCE-TW5

3135

106

ZPD182KCE-TWD

3135

106

ZPD182KCE-TWE

3135

106

Step 3. Mount the Replacement Compressor

Do not remove the dust cover or rubber shipping plugs until all other system

connections are complete (i.e. new liquid line filter drier(s) installed and all tubing

changes made - see Steps 4 and 5). The amount of time the compressor is open

to the atmosphere must be kept to a minimum.
Use the new mounting grommets and sleeves that are shipped with the

compressor to mount it. The sleeves will prevent over compression of the

grommets. Re-use the mounting bolts from the compressor that was removed. The

mounting bolts will bottom out when tight.

Step 4. Install New Filter Driers (Select procedure that applies.)

IF the oil measured in Step 2 was not significantly less than the amount shown in

the table above or the test for acid in

Step 2 did NOT indicate burnout , install

a new R-410A refrigerant liquid line filter drier. The filter drier must be rated for

no less than 600 psig and be the proper size for the circuit. Because R-410A

refrigerant requires POE oil which absorbs moisture quickly, it is important to

3.0 Maintenance/Service Procedures - Unit & Cooling (cont'd)

Advertising
This manual is related to the following products: