Form O-Y P/N 273647R1, Page 31

If equipped with optional preheat, one or two 10kw electric heat modules are located

in the inlet air stream. Preheat operation is controlled by the system controller and is

commanded ON when the supply air discharge sensor signals a temperature reading

of 33°F (0.56°C).

Optional Frost Control Electric Element

Part Number

Voltage

273793

230/1/60

272505

208-230/3/60

272506

460/3/60

272507

575/3/60

Optional Preheat

(frost Control)

Wheel Supply Air

Discharge Sensor

The supply air discharge sensor monitors wheel operation and if equipped with pre-

heat, controls operation of the electric heat module(s). The supply air discharge sen-

sor is a probe sensor located in the wheel discharge.
Service: Check the wiring. If the sensor needs to be replaced, use only a factory

authorized replacement part designed for the purpose.

FIGURE 22 - Location of the Wheel Supply Air Discharge Sensor

Temperature Sensor

in Wheel Supply

Airstream

Temperature Sensor,

P/N 222753

Advertising