3.2 Supply Fan

and Variable

Frequency Drive

Fan motors are permanently lubricated; lubrication is not required, During

maintenance, remove any accumulation of dirt and grease. The fan CFM was

checked and balanced at startup. To recheck, follow the instructions in the installation

manual, Form I-Y, Paragraph 10.3.
If service is required, the supply fan is mounted on a sled that will slide out of the

cabinet.
Instructions for sliding out the supply fan:

1. Turn off the power and lock the disconnect switch.
2. Open the supply fan door and the cooling cabinet door.
3. The flexible duct joining the supply fan to the cooling compartment is visible.

Locate the metal flange holding the duct to the cabinet. Remove the two screws

from fan sled (locations shown in picture on the left) and the flange to free the duct

so that it can be slid out with the fan.

4. Open the electrical box on the fan. Mark and disconnect the wires.
5. Carefully slide the complete fan sled out of the cabinet.
6. When service is complete, slide the sled into the cabinet. Re-connect the wires

and re-attach the flange to hold the flexible duct in place. If the pressure tube was

removed during service, be sure to re-attach it securely. Reinstall two screws into

the fan sled.

Variable Frequency

Drive

Approx fan sled

screw locations

Function: When the main controller calls for supply fan operation, a variable fre-

quency drive (VFD) responds to operate the motor.
The VFD is located on the high voltage electrical panel (See

FIGURE 1, page 4).

Control of the variable frequency drive module is dictated by the main controller, and

depending on what was ordered, can function in response to temperature, CO

2

, or

pressure controls. !
Service: Remove any dirt or dust. Check the wire connections. If a VFD needs

to be replaced, use a factory-authorized replacement designed for the application.

Supply fan in "slide

out" position

Code

Control Panel Display

1

LCD display -

Divided into 5

areas

Upper left - Control location
Upper right - unit of the displayed value
Center - Parameters and signal values, menus and alarm codes
Lower left and center - Operation state
Lower right - Motor rotation

2

RESET / EXIT

Resets faults and exits to higher menus

3

MENU / ENTER Menu selection and saves value

4

UP

Scrolls up through menu / list
Increases value of parameters or reference values

5

DOWN

Scrolls down through menu / list
Decreases value of parameters or reference values

6

LOC / REM - VFD controlled by main controller

7

DIR - Changes the direction of the motor

8

STOP - Stops the drive

9

START - Starts the drive

9) START

7) DIR

3) MENU / ENTER

5) DOWN

4) UP

8) STOP

6) LOC / REM

2) RESET / EXIT

1) LCD Display

Variable Frequency

Drive Model ACS355

Variable Frequency

Drive Model ACS550

FIGURE 4 - VFD

Display