3 vent maintenance and operation – Reznor YDSA Operation Manual User Manual

Page 40

Advertising
background image

Form O-Y, PN 273647R1, Page 40

Vent Maintenance

Remove dirt and grease from the venter motor housing. The venter motor is perma-

nently lubricated; do not lubricate. Carefully clean the venter wheel assembly, being

cautious not to bend the wheel.
Check the vent at least once a year. Clean the terminal screen. If equipped with

optional vertical vent extension, inspection should include all joints, seams, and the

terminal. Replace any defective parts.
Venter Speed Board Options AG73 and AG74 - Modulating gas controls have a

proprietary electronically controlled venter system that provides the required volume

of combustion air and correct gas pressure to maintain thermal efficiency during

periods of modulation. Change of venter speed is controlled by an electronic board

located on the heat section control panel (See

FIGURE 23, page 32). The venter sys-

tem always operates at high speed during pre-purge and post-purge periods. Speed

selection occurs after there is a call for burner ignition.

Venter Speed Board

5.3 Vent

Maintenance

and Operation

Maintenance

Instructions for the

Venter Motor and

Wheel

FIGURE 28 - Venter

Wheel Position on

the Shaft (High

Efficiency Models)

Remove dirt and grease from the motor casing, the venter housing, pressure sensing

tap, and the venter wheel. Venter motor bearings are permanently lubricated.

Follow these instructions for replacement of the venter motor and wheel assembly.

Keep all hardware removed to be used in re-assembling and installing the replace-

ment parts.

1. Turn off the gas and disconnect the electric power.

2. Open the burner/control compartment door panel.

3. Disconnect the two or three venter motor wires at the DSI control or the venter

speed control board, capacitor wires at the capacitor (if applicable), and ground

screw (located on the control panel).

4. On high efficiency (90%) condensing heat section, holding the venter motor,

remove the screws that attach the venter motor mounting plate to the venter

housing. Remove the motor and wheel assembly from the heater.
On standard efficiency (80%) non-condensing heat section, remove the venter

housing assembly by removing the screws that attach it to the flue wrapper.

5. Re-assemble with the replacement venter motor and wheel assembly. See

FIGURE 28 shown below for correct spacing. If there is a motor plate gasket,

check it. If the gasket is damaged, replace it.

6. Follow the wiring diagram to connect the venter wires.

7. Close the door panel. Restore power to the heater and turn on the gas. Light,

following the instructions on the lighting instruction plate. Check for proper

operation.

NOTES:
1) Manufacturer recommends replacing

venter motor capacitor when replacing venter

motor.

2) On standard efficiency (80%) non-

condensing heat section, venter motor and

wheel assembly cannot be disassembled.

Motor plate to wheel

G150, G225, G300, G302

G372, G452, G525, G602

Venter

Motor

Venter Wheel

Motor Plate (and Motor

Plate Gasket, P/N 221163)

.31"

5.0 Maintenance/Service Procedures - Gas Heat Section (cont'd)

Advertising