Determine zone module air quantity as described in the

Selection Procedure (1000 cfm)

2

Enter curve at determined zone moduie air quantity Project left

to intersect with entering air temperature curve (70 F)

3

From this intersection, project up to intersect with entering

water temperature (180 F)

4. From this intersection,project right to intersect with Water Flow

Rate (4 gpm).

5 From this intersection, project down to read Zone Module

Fleating Capacity (49,500 Btuh)

When

using

soiution

mixtures

above

20%

glycol

concentration,

reduce the capacity using the correction factor

i e If 30% glycol concentration applies to the example,

Corrected Zone Module Fleating Capacity

= Zone Module Fleating Capacity x Correction Factor

= 49,500

X

0 985

= 48,750 Btuh

See Fig 36 The Ap at 4 gpm is 8 2 psig

Fig. 35 — Hot Water/Glycol Heating Capacities (Hot Water with 20% Ethylene Glycol Solution)

Fig. 36 — Module Pressure Drop

47