A warning, Warning, Field – Carrier 38GNA User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 2—Tubing Data

REFRIGERANT LINE LENGTH

UNIT SIZE

10 to 50 ft

51 to 100 ft

Diameter (In.)

Suction

Liquid

Suction

Liquid

018, 024

5/8

3/8

3/4

3/8

1. Maximum vertical separation for evaporator over condensing unit is 50 ft.
2. Over 50 ft of vertical separation, the condensing unit must be located above

the evaporator. For requirements beyond 50 ft, obtain information from

distributor or consult Long-Line Application Guideline.
3. Charge adjustment is required when using more than 25 ft of tubing. See

Refrigerant Charging information on unit rating plate.
4. Do not use larger than 3/4-in. suction line.

If accessory tubing package or evaporator coil has been open for

more than 5 minutes, evacuate evaporator coil and tubing system.

Always evacuate if field-supplied tubing is used. See Evacuation
section.

Ensure field-supplied tubing is of refrigerant grade. Insulate the

suction line with insulation that has an adequate vapor barrier.
Evacuate tubing.

1. Run refrigerant lines as directly as possible, avoiding any

unnecessary turns and bends.

2. Tape the liquid line to the top of the insulated suction line for

support.

3. Suspend the refrigerant lines so they do not damage the

insulation on the suction line and do not transmit vibration to

the structure.

4. If the refrigerant lines are too long, the excess may be cut off.

5. Connect tubing to the condensing unit. The refrigerant tubing

and evaporator coil should be leak tested upon completion.

When making piping connections, be sure to provide clearance at

unit for electrical connection.

Connect suction and liquid refrigerant lines to condensing unit.

(See Fig. 1.) Make suction line connection first.

Two grommets are provided to seal the gap between refrigerant
lines and unit casing. Cut small grommet, slip it over liquid line

and push it into casing opening. Gap around suction line is sealed

in same manner except that suction line insulation must be cut and

pushed back before grommet can be slipped into place. (See Fig.

4.)

FIELD TUBING CONNECTIONS - All models are equipped
with 3/8-in. liquid and 5/8-in. suction back seated service valves

with mechanical flare field connections. Factory-supplied 3/8-in.

to 3/8- in. and 5/8-in. to 5/8-in. flare-to-sweat adaptor tubes are

provided. Field-supplied couplings are required for tubing pack­

ages exceeding 50-ft long-line applications.

LEAK TESTING — No installation is complete until all field and

factory joints have been checked for leaks.

1. Remove valve stem caps from both service valves and check

to be sure valves are front seated (turned clockwise). Remove

service port caps.

2. Attach gage manifold to service ports of service valves and

purge hoses.

3.

Pressurize evaporator coil and interconnecting refrigerant

tubing with vapor from an external refrigerant cylinder of
R-22 until the system and cylinder pressure are equalized.

NOTE:

NEVER USE A UNIT CHARGE FOR LEAK TEST­

ING.

4. Leak test with an electronic detector, a halide torch, or a liquid

soap solution.

5. Recover refrigerant and repair any leaks.

6. If system is free of leaks, prepare unit for operation.

EVACUATION

1. Connect evacuation equipment to system gage manifold.

2.

Evacuate system following appropriate steps for type of

evacuation equipment used.

3. Pressurize system with refrigerant to 10 psig and open (turn

counter-clockwise) both service valves.

4. Remove gage manifold. Replace valve stem and service port

caps on both service valves.

Step

4

—Make Electrical Connection

Field wiring must comply with local and national fire, safety and
electrical codes. Voltage to unit must be within range of 253v to

187v. Refer to nameplate for other electrical data. Contact local

power company for correction of improper line voltage.

Step 3—^Test Unit

A

WARNING

According to NEC, ANSI/NFPA 70, and local codes, the
cabinet must have an uninterrupted or unbroken ground, to

minimize personal injury if an electrical fault should occur.

The ground may consist of electrical wire or metal conduit
when installed in accordance with existing electrical codes.

Failure to follow this warning could result in an electric

shock, fire, or death.

See unit’s rating plate for recommended fuse size. When making

electrical connections, provide clearance at unit for refrigerant

piping connections.

BRANCH CIRCUIT DISCONNECT - Install a branch circuit

disconnect per NEC of adequate size to handle unit starting

current. Locate disconnect within sight from and readily accessible
from unit, per Section 440-14 of the NEC.

LINE POWER LEADS

Extend leads from disconnect per NEC into unit through hole

provided in service panel. (See Fig. 1.) Connect ground lead to

ground lug in control box for safety. Connect line power leads to

contactor screw terminals LI and L2. (See Fig. 5 or 6.) Contactor

terminals are approved for use with copper

field

wiring.

CONTROL POWER (24V) — Use furnace or fan coil trans­

former as 24v supply for system. Transformer must have a

minimum capacity of 30 va. Bring control wiring through hole in

unit service panel and connect to pigtails from unit contactor.

Contactor pigtails are labeled Y and C. Refer to Fig. 5 or 6 for

system control circuit connections.

Advertising