Carrier 38GC User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

(Mate one set of

MECHANICAL CONNECTION

connections at a time).

1. Loosen nut on Compatible Fitting one turn. Do

not remove. Loosen tube clamp.

2. Remove rubber plug and be sure 0-ring is in the

groove inside the Compatible Fitting.

3. Cut tubing to correct length.
4. Use gage on tag attached to service valve to

mark tube end for correct insertion depth.

Insert tube into Compatible Fitting until it

bottoms. (Tube should be inserted at least as
far as mark on tubing.)

5. Tighten nut until it bottoms

on back coupling

flange. Tighten tube clamp.

SWEAT CONNECTION (use refrigerant grade

tubing).

1. Remove locking nut and rubber 0-iing from

inside of fitting. Loosen tube clamp entering

condensing unit base.
Cut tubing to correct length.

Insert tube into Compatible Fitting. Wrap top

and bottom of service valves in wet cloth to
prevent damage by heat. Solder with low
temperature (450 F) silver alloy solder. Tighten
tube clamp.

Evacuate or purge system with field-supplied
refrigerant.

2

.

3.

4.

ELECTRICAL DATA AND WIRING

Wiring

— Field wiring must comply with local and

national codes. Install a branch circuit fused
disconnect of adequate size to handle starting

current. When making electrical connections, pro­

vide clearance at unit for refrigerant piping

connections.

LINE POWER is brought thru unit base pan flange

and thru hole provided in control box (Fig. 1). On

38GC101, 38GF106 (230-v, 1-ph) and 38GF103,

104 (208- and 230-v, 3-ph) units, line power

connections are made to pigtails supplied with

unit. Use approved splice connector. Do not use

aluminum field wire for splice connections unless

copper to aluminum adapters is used, and correct

wiring techniques are followed.

On all other models connect line power to

contactor screw power terminals as indicated on

unit label diagram, i.e., connect power leads to

contactor terminals 21 and 23 on single-phase
units, or 21, 22, and 23 on 3-phase units.

On all 3-phase units, do not connect a grounded

high voltage leg to control circuit pigtail or
terminal; connect leg to compressor pigtail or
terminal. See label diagram.

CONTROL POWER is brought thru unit base pan

(Fig. 1), and thru 7/8-in. hole into low voltage

section of control box. All connections are made

to pigtails supplied with unit (Fig. 2). Where
supply voltage exceeds 150 volts to ground, or
local codes require it, ground 24-volt control

circuit at field splice C.

Table 4 — Refrigerant Piping Data

Crankcase

heater

(standard

on

GF),

liquid

line

filter-drier

(standard

on

GF)

and

start

capacitor

with

relay

(accessory

on

GC101,

102,

103

and

GF102)

required Reduce liquid line size one diameter (mini /4-in OD) when evaporator

is below condensing unit

TXV

Thermal

Expansion

Valve

Cap. Tube — Capillary Tube

*3/4-in on 38GF.

Advertising
This manual is related to the following products: