Additional features, Remote programming and monitoring – AMETEK XFR 2800 Watt Series User Manual

Page 98

Advertising
background image

Specifications

A-8

TM-F2OP-C1XN-01

Additional Features

Remote Programming and Monitoring

Switching Frequency

nominal 31 kHz (62 kHz output ripple).

Output Hold-up Time

Greater than 10 ms with interruption of
AC line, for nominal AC input and
full load.

Maximum Voltage Differential
from either output to safety
ground

±600 Vdc

Insulation Resistance

Input to chassis: >30 M

Ω, with 500 Vdc;

Output to chassis: >20 M

Ω, with

1000 Vdc.

Isolation Voltage

Input to output: 1350 Vac

Remote Start/Stop and
Interlock

2.5-15 V signal or TTL-compatible input,
selectable logic. TTL input impedance: 2 k
(in series with one diode drop).

Remote Analog Programming
(Full Scale Input)

Voltage and current programming inputs
(source must be isolated): 0-5 k, 0-10 k
resistances; 0-5 V, 0-10 V (default) voltage
sources. Input impedance (V and I):
approximately 100 k.

Remote Monitoring

Output voltage and current: 0-5 V, 0-10 V
(default);
Output impedance (V and I): approx 221

Ω.

Output short circuit current: approx. 50 mA.

Remote Programming and
Monitoring Accuracy

1% zero to full scale output for the default
range.

Maximum Remote Sense Line
Drop Compensation

5 V/line (Line drop is subtracted from total
voltage available at supply output.)

Optional Isolated Program
and Readback (V&I)

0-5 V (ISOL interface); input impedance:
200 k; output impedance: 221

Ω.

Optional Digital Control

RS-232, GPIB interfaces