2 universal input — configured as analog input, Universal input, Configured as analog input – Contemporary Control Systems BAScontrol20 User Manual User Manual

Page 15

Advertising
background image

TD100700-0MB

15

4.2 Universal Input

— Configured as Analog Input

An analog input can measure voltage in the range of 0

–10 VDC or it can measure

current in the range of 0

–20 mA with a 500 Ω external resistor. Transmitters that

produce an elevate

d “zero” such as 2–10 VDC or 4–20 mA can be measured as

well. Using the web page, configure the input for voltage. When set as a voltage
input, the input impedance is 1 MΩ.

With voltage measurement, connect the more positive voltage to point A and the less
positive to common C as shown in

Figure 4

. On three-wire devices such as damper

actuators, the output signal is referenced to the damper’s power supply common.
That common must be at the same reference as the BASC20 common. Notice the
connections in the diagram. In this situation it is only necessary to attach the
transmitter output to point A on the BASC20 input.

Figure 4

— Analog Input Connections

When measuring current from two-wire transmitters, remember the BASC20 sinks
current to ground. A 50

0 Ω resistor is applied between points A and C on the input.

To measure current, it must be driven into point A with respect to point C.

Care should be exercised when connecting to a three-wire current transmitter.
These are usually non-isolated devices between the power source and signal output.
The BASC20 will sink current from its input to ground so the transmitter must source
current from a positive potential to ground. If the three-wire transmitter works in this
manner, it can be accommodated.

Four-wire transmitters usually have isolation between power supply and signal
output so their output stage can usually be treated as a two-wire transmitter.

Advertising