Absolute encoder installation

3.1

Settings inside the encoder

The encoder node address and bus termination must be

configured during commissioning of the device. This is done by

removing the back cover, i.e. screwing off the three screws at the

rear of the encoder.

3.1.1

Node address

The node address of the encoder can be set via two decimal

rotary switches located inside the back cover. The weighting, x10

or x1 are specified beside the switches. Permissible address

range is between 0 and 99 but the lower addresses 0 to 2 are

usually used by the master and not recommended to be used by

the device. Each address used in a PROFIBUS network must be

unique and may not be used by other devices.

The device address is only read and adopted when the encoder

power supply is switched on. A restart of the encoder is therefore

required in order to adopt changes done to the address settings.

Figure 7

PCB-view of a cable gland encoder

Example

: If the node address shall be set to 85, the left (x10)

switch shall be set to 8 and the right (x1) switch shall

be set to 5.