12

HC900 Hybrid Controller Communications User Guide

Revision 10

12/07

REGISTER N
(High)

REGISTER N+1
(Low)

High

Low

High

Low

FP L - Floating Point Little Endian Format:

S=Sign E=Exponent M=Mantissa

E0 M22 M21M20 M19 M18 M17 M16

Bit 23

Bit 16

S E7 E6 E5 E4 E3 E2 E1

Bit 31

Bit 24

M7 M6 M5 M4 M3 M2 M1 M0

Bit 7

Bit 0

M15 M14 M13 M12 M11 M10 M9 M8

Bit 8

Bit 15

REGISTER N
(High)

REGISTER N+1
(Low)

High

Low

High

Low

FP LB - Floating Point Little Endian with Byte Swapped Format:

S=Sign E=Exponent M=Mantissa

E0 M22 M21M20 M19 M18 M17 M16

Bit 23

Bit 16

S E7 E6 E5 E4 E3 E2 E1

Bit 31

Bit 24

M7 M6 M5 M4 M3 M2 M1 M0

Bit 7

Bit 0

M15 M14 M13 M12 M11 M10 M9 M8

Bit 8

Bit 15

Figure 3-1 IEEE Floating Point Formats

Table 3-2 IEEE Floating Point Number Examples in FP B Format

Register N

Register N+1

Value

(decimal)

IEEE FP B

MSB LSB

high

low

high

low

100.0 42C80000h

42h C8h 00h 00h

55.32 425D47AEh

42h 5Dh 47h AEh

2.0

40000000h

40h

00h

00h

00h

1.0

3F800000h

3Fh

80h

00h

00h

-1.0 BF800000h

BFh

80h

00h 00h