Honeywell HC900 User Manual

Page 69

Advertising
background image

Revision 10

HC900 Hybrid Controller Communications User Guide

61

12/07

Fixed
Address
(hex)

Fixed
Register
(decimal)

Parameter

Access

Notes

1F10

7953

Jog Segment

R/W

Floating Point
Writing to this register is only permissible in
the reset or ready mode

1F12

7955

Loop Start

R/W

Floating Point
0 indicates no loop.
Writing to this register is only permissible in
the reset or ready mode

1F14

7957

Loop End

R/W

Floating Point
0 indicates no loop.
Writing to this register is only permissible in
the reset or ready mode

1F16

7959

Repeats

R/W

Floating Point
0 indicates loop forever.
Writing to this register is only permissible in
the reset or ready mode

1F3A

7995

Time Units**

R/W

Bit Packed
Bit 0:

Reserved

1: minutes

2:

hours

3-15: Unused

1F3B

7996

Ramp Units**

R/W

Bit Packed
Bit

0:

0:Time; 1:Rate

Bit 1-15:

Unused

Writing to this register is only permissible in
the reset or ready mode

1F3C

7997

Guaranteed Soak Type **

R/W

Bit Packed
For selection of Soak (or Hold) guarantee –
Per Segment (requiring selection per
segment in a table)
Bit

0: per segment

1: all soaks

2: all segments

3-15:

Unused

None if none of the bits is set
Writing to this register is only permissible in
the reset or ready mode