HC900 Hybrid Controller Communications User Guide

Revision 10

12/07

Loop type

Fixed
Address
(hex)

Fixed
Register
(decimal)

Parameter Name

PIDOn

/
Off

Carb3Pos AMB

Access Notes

0062

0099

Three Position Step
Motor Deadband

R/W

Floating Point in percent

0064

0101

Reset #2

9

9

R/W

Floating Point in Repeats/Minute or Minutes/Repeat
as configured in the HC900.

0066

0103

Rate #2

9

9

R/W

Floating Point in Minutes

0068

0105

Cycle Time for Analog
Scan

9 9 9 9

9

R

Floating Point in Seconds

006A

0107

LSP #1

9 9 9 9

R/W

Floating Point in Engineering Units

006C

0109

LSP #2

9 9 9 9

R/W

Floating Point in Engineering Units.

006E

0111

Alarm #2 SP #1

9 9 9 9

9

R/W

Floating Point in Engineering Units.

0070

0113

Alarm #2 SP #2

9 9 9 9

9

R/W

Floating Point in Engineering Units.

0074

0117

SP Low Limit

9 9 9 9

R/W

Floating Point in Engineering Units. Operator Limit

0076

0119

SP High Limit

9 9 9 9

R/W

Floating Point in Engineering Units. Operator Limit

0078

0121

Working Set Point

9 9 9 9

R/W

Floating Point in Engineering Units.
On a write to this register the instrument will update
the proper set point according to the loop’s currently
selected set point.

007A

0123

Output Low Limit

9

9

9

R/W

Floating Point in Engineering Units.

007C

0125

Output High Limit

9

9

9

R/W

Floating Point in Engineering Units.

007E

0127

Output Working Value 9 9 9

9

9

R/W

Floating Point in Engineering Units.

0086 0135 Ratio

9

9

R/W

Floating Point in Engineering Units.

0088

0137 Bias

9

9

9

R/W

Floating Point in Engineering Units. Auto/Man bias
block, value is Read-Only

008A

0139 Deviation

9 9 9 9

R

Floating Point in Engineering Units.
(SP-PV)

008E

0143

Manual Reset

9

9

R/W

Floating Point in Engineering Units.

0090

0145

Feed-forward Gain

9

9

R/W

Floating Point in Engineering Units.

0092

0147

Local Percent Carbon
Monoxide

9

R/W

Floating Point in Engineering Units.

0094

0149

Furnace Factor

9

R/W

Floating Point in Engineering Units.

0096

0151

Percent Hydrogen

9

R/W

Floating Point in Engineering Units.

0098

0153

On/Off Output
Hysterisis

9

R/W

Floating Point in percent of input span

009A

0155

Carbon Potential
Dewpoint

9

R/W

Floating Point in Engineering Units

009C

0157

Three Position Step
Motor Time

9

R/W

Floating Point in seconds

00F7

0248

Enable/Disable Fuzzy 9

9 9

R/W

Bit

Packed

Bit 0: 0:Disable; 1:Enable

00F8

0249

Demand Tune
Request

9

9 9

R/W

Bit Packed (one shot action, activates autotuning
until autotuning completed)
Bit 0: 0:Off; 1:On
Bit 1-15: Unused

00F9

0250

Anti-soot set point limit
enable

9 R/W

Bit

Packed

Bit 0: 0:Off; 1:On
Bit 1-15: Unused

00FA

0251

Auto/Manual State

9 9 9 9

9

R/W Bit

Packed

Bit 0: 0:Manual; 1:Auto
Bit 1-15: Unused