Honeywell HC900 User Manual
Page 58
50
HC900 Hybrid Controller Communications User Guide
Revision 10
12/07
Loop type
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name
PIDOn
/
Off
Carb3Pos AMB
Access Notes
0062
0099
Three Position Step
Motor Deadband
R/W
Floating Point in percent
0064
0101
Reset #2
9
9
R/W
Floating Point in Repeats/Minute or Minutes/Repeat
as configured in the HC900.
0066
0103
Rate #2
9
9
R/W
Floating Point in Minutes
0068
0105
Cycle Time for Analog
Scan
9 9 9 9
9
R
Floating Point in Seconds
006A
0107
LSP #1
9 9 9 9
R/W
Floating Point in Engineering Units
006C
0109
LSP #2
9 9 9 9
R/W
Floating Point in Engineering Units.
006E
0111
Alarm #2 SP #1
9 9 9 9
9
R/W
Floating Point in Engineering Units.
0070
0113
Alarm #2 SP #2
9 9 9 9
9
R/W
Floating Point in Engineering Units.
0074
0117
SP Low Limit
9 9 9 9
R/W
Floating Point in Engineering Units. Operator Limit
0076
0119
SP High Limit
9 9 9 9
R/W
Floating Point in Engineering Units. Operator Limit
0078
0121
Working Set Point
9 9 9 9
R/W
Floating Point in Engineering Units.
On a write to this register the instrument will update
the proper set point according to the loop’s currently
selected set point.
007A
0123
Output Low Limit
9
9
9
R/W
Floating Point in Engineering Units.
007C
0125
Output High Limit
9
9
9
R/W
Floating Point in Engineering Units.
007E
0127
Output Working Value 9 9 9
9
9
R/W
Floating Point in Engineering Units.
0086 0135 Ratio
9
9
R/W
Floating Point in Engineering Units.
0088
0137 Bias
9
9
9
R/W
Floating Point in Engineering Units. Auto/Man bias
block, value is Read-Only
008A
0139 Deviation
9 9 9 9
R
Floating Point in Engineering Units.
(SP-PV)
008E
0143
Manual Reset
9
9
R/W
Floating Point in Engineering Units.
0090
0145
Feed-forward Gain
9
9
R/W
Floating Point in Engineering Units.
0092
0147
Local Percent Carbon
Monoxide
9
R/W
Floating Point in Engineering Units.
0094
0149
Furnace Factor
9
R/W
Floating Point in Engineering Units.
0096
0151
Percent Hydrogen
9
R/W
Floating Point in Engineering Units.
0098
0153
On/Off Output
Hysterisis
9
R/W
Floating Point in percent of input span
009A
0155
Carbon Potential
Dewpoint
9
R/W
Floating Point in Engineering Units
009C
0157
Three Position Step
Motor Time
9
R/W
Floating Point in seconds
00F7
0248
Enable/Disable Fuzzy 9
9 9
R/W
Bit
Packed
Bit 0: 0:Disable; 1:Enable
00F8
0249
Demand Tune
Request
9
9 9
R/W
Bit Packed (one shot action, activates autotuning
until autotuning completed)
Bit 0: 0:Off; 1:On
Bit 1-15: Unused
00F9
0250
Anti-soot set point limit
enable
9 R/W
Bit
Packed
Bit 0: 0:Off; 1:On
Bit 1-15: Unused
00FA
0251
Auto/Manual State
9 9 9 9
9
R/W Bit
Packed
Bit 0: 0:Manual; 1:Auto
Bit 1-15: Unused