12/07
6.16 Device Control
Summary
This table contains addresses for the Device Control group #1.
See the Device Control Register Maps in Table 6-1 for starting and ending addresses (hex) for Device
Control #2 through Device Control #16 Map Addresses.
The Modbus Device Control number address for a Device Control can also be obtained from the Hybrid
Control Designer report.
Function Code Support:
Reads – Function Code 3
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point )
Writes – Function Code 6 for presetting an integer value
For custom addresses view or print a report in HC Designer.
Table 6-26 Device Control parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name
Access Notes
6B00
27393
Reset Request
W
Unsigned 16 Integer
Data Ignored
6B01
27394
Status Indicator
R
Bit Packed
Bits 0 – 6: Device Control State
Bit 0: Ready: 0=NO, 1=YES
Bit 1: Prestart: 0=NO, 1=YES
Bit 2: Starting: 0=NO, 1=YES
Bit 3: Running: 0=NO, 1=YES
Bit 4: Stopping: 0=NO, 1=YES
Bit 5: Disabled: 0=NO, 1=YES
Bit 6: Failed: 0=NO, 1=YES
Bit 7: Run Request Input State; 0=OFF, 1=ON
Bit 8: Device Feedback Started; 0=NO, 1=YES
Bit 9: Device Failed; 0=NO, 1=YES
Bit 10: Automatic Reset; 0=Manual, 1=Auto
Bit 11-15: Unused
6B02 27395 Remaining
Delay
Time
R
Floating Point in Seconds
6B04
27397
Start Delay
R/W
Floating Point in Seconds
6B06
27399
Stop Delay
R/W
Floating Point in Seconds
6B08
27401
Feedback Fail Delay
R/W
Floating Point in Seconds