A.6.1 setup input, A.6.1, Setup input – Liebert Universal Monitor User Manual

Page 114: Section a.6.1

Advertising
background image

Setup Menu

106

A.6.1 Setup Input

For details on this feature, see 9.3 - Setup System - Setup Input.

Setup Input - Main Board Outputs

SETUP INPUT

Setup for discrete

input points

Select input to edit

INPUT

DEFINITION

1=INPUT_01 NO-EV-NL-00:01
2=INPUT_02 NO-AL-L -00:01
3=INPUT_03 NC-EV-NL-00:01
4=INPUT_04 NO-AL-L -00:01
5=INPUT_05 NC-AL-L -00:01
6=INPUT_06 NO-EV-NL-00:01
7=INPUT_07 NO-AL-L -00:01
8=INPUT_08 NC-EV-NL-00:01
9=EXPANSION BOARD INPUTS
0=RETURN TO SETUP MENU
I=RETURN TO MAIN MENU

SELECT A NUMBER:1

****************************
NO=NORMALLY OPENED
NC=NORMALLY CLOSED

EV=EVENT
AL=ALARMABLE

NL=NOT LATCHED
L =LATCHED

MIN:SEC=DELAY TIME BEFORE

INPUT WILL TRIGGER

NOTE:EVENT CANNOT BE LATCHED
****************************

>CHANGE LABEL(8 CHARACTERS MAX).
>[INPUT_01]
>[
>COMMAND SUCCESSFUL

>IS INPUT NORMALLY OPENED(NO) OR NORMALLY CLOSED(NC)?
>[NO]
>[
>COMMAND SUCCESSFUL

>IS INPUT AN ALARM(AL) OR EVENT(EV)?
>[EV]
>[
>COMMAND SUCCESSFUL

>IS ALARM LATCHED-YES(Y) OR NO(N)?
>[N]
>[
>COMMAND SUCCESSFUL

>DELAY TIME BEFORE TRIGGER (MM:SS)?
>[00:01]
>[
>COMMAND SUCCESSFUL