System and Control Options

51

9.5.4 Change 4 mA Value

For the 4 mA value, enter the smallest value for the range of the sen-

sor—for example, 50°F for a temperature sensor with a range of 50°F

to 90°F.
The default value for each sensor is -999.9. Values that can be entered

range from -999.9 to +999.9.
To enter a new value:

• From the Setup Sensor Menu, choose 4 mA for the selected sensor

and press Enter ↵ .

• To change the 4 mA value:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.

9.5.5 Change 20 mA Value

For the 20 mA value, enter the largest value for the range of the sen-

sor—for example, 90°F for a temperature sensor with a range of 50°F

to 90°F.
The default value for each sensor is +999.9. Values that can be entered

range from -999.9 to +999.9.
To enter a new value:

• From the Setup Sensor Menu, choose 20 mA for the selected sen-

sor and press Enter ↵ .

• To change the 20 mA value:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.

9.5.6 Change Offset Value

For the Offset value, enter an adjustment factor—for example, if the

sensor reading shows 70°F when the actual temperature is 75°F, the

offset might be 5°F.
The default Offset value for each sensor is +000.0. Values that can be

entered range from -999.9 to +999.9.
To enter a new value:

• From the Setup Sensor Menu, choose Offset for the selected sensor

and press Enter ↵ .

• To change the Offset value:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED : Y
LABEL: ROOM_TMP

↑ ↓=NEXT

=SELECT

UNITS: DEG

> 4 mA: -999.9

20 mA: +999.9
OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: -0999.9
HIGH SETPT: +0999.9
SENSOR DELAY: 00:01

Change 4 mA Value

CHANGE 4 mA VALUE

4 mA: +050.0

↑ ↓=SELECT

=NEXT/END

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED : Y
LABEL: ROOM_TMP

↑ ↓=NEXT

=SELECT

UNITS: DEG
4 mA: +050.0

> 20 mA: +999.9

OFFSET: +000.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: -0999.9
HIGH SETPT: +0999.9
SENSOR DELAY: 00:01

Change 20 mA Value

CHANGE 20 mA VALUE

20 mA: +090.0

↑ ↓=SELECT

=NEXT/END

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED : Y
LABEL: ROOM_TMP

↑ ↓=NEXT

=SELECT

UNITS: DEG
4 mA: +050.0
20 mA: +090.0

> OFFSET: +000.0

ALARM/EVENT: AL
LATCHED: N
LOW SETPT: -0999.9
HIGH SETPT: +0999.9
SENSOR DELAY: 00:01

Change Offset Value

CHANGE OFFSET VALUE

OFFSET: +005.0

↑ ↓=SELECT

=NEXT/END