System and Control Options

45

9.2

Setup System - Overview

The Setup System screen displays seven options that allow you to configure input and output

devices and their relationships, the common alarm, the modem, pagers to be dialed when alarms

occur, and a variety of system details, such as login password and system date and time:

• Setup Input
• Setup Common Alarm
• Setup Sensor
• Setup I/O Matrix
• Setup Output
• Setup Modem & Pagers
• Setup System Info
• Setup Exp Board

9.3

Setup System - Setup Input

The Universal Monitor has eight digital input points that may be

configured individually. If the optional Expansion Board is used, an

additional 16 digital inputs may also be configured. These inputs may

have a wide variety of Liebert or other manufacturers’ equipment

connected for monitoring.
To configure a digital input:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑ ↓

to

choose System and

Control, then press Enter ↵ (see 9.1 - Login for help).

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑ ↓

to

choose

Setup System, then press Enter ↵ .

Select a Digital Input to Configure

• From the Setup System Menu, shown at right, use the arrows

↑ ↓

to

choose Setup Input and press Enter ↵ .

• From the Select Input Menu, choose the input you want—for exam-

ple, Input_01—and press Enter ↵ .

Table 21 shows the digital input features you may change, along with

the default settings: you may change the name of the input, define it as

normally open or closed, and specify it as alarmable or as an event.

• Alarmable inputs may be defined as either Unlatched or Latched.
• Event status allows you to monitor a digital input’s state—and use a change in state to initiate an

action through an output, if desired—without triggering an alarm. Events are always Unlatched.

• You may also specify a time delay before the Universal Monitor responds to an alarm or event.

Use the steps following Table 21 to change the default settings for any digital input.
Table 21

Default settings - digital inputs

Feature

Default

Other Options

LABEL

INPUT_01

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

NL (Unlatched) / N (No)*

L (Latched) / Y (Yes)*

DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.

Settings - Select Input Menu
(see Section 9.3)

When configuring an input
(see Section 9.3.4)

Unlatched

NL (Not Latched)

N (No, not latched)

Latched

L (Latched)

Y (Yes, latched)

Setup System Menu

> SETUP INPUT

SETUP COMMON ALARM
SETUP SENSOR
SETUP I/O MATRIX

↑ ↓=NEXT

=SELECT

SETUP OUTPUT
SETUP MODEM&PAGERS
SETUP SYSTEM INFO
SETUP EXP BOARD

Select Input Menu

SELECT INPUT

> INPUT_01 NO-AL-NL

INPUT_02 NO-AL-NL

↑ ↓=NEXT

=SELECT

INPUT_03 NO-AL-NL
INPUT_04 NO-AL-NL
INPUT_05 NO-AL-NL
INPUT_06 NO-AL-NL
INPUT_07 NO-AL-NL
INPUT_08 NO-AL-NL
INPUT_09

NO-AL-NL

INPUT_10

NO-AL-NL

INPUT_11

NO-AL-NL

INPUT_12

NO-AL-NL

INPUT_13

NO-AL-NL

INPUT_14

NO-AL-NL

INPUT_15

NO-AL-NL

INPUT_16

NO-AL-NL

INPUT_17

NO-AL-NL

INPUT_18

NO-AL-NL

INPUT_19

NO-AL-NL

INPUT_20

NO-AL-NL

INPUT_21

NO-AL-NL

INPUT_22

NO-AL-NL

INPUT_23

NO-AL-NL

INPUT_24

NO-AL-NL

NOTE: INPUT_09 - INPUT_24

for optional Expansion Board