System and Control Options

53

9.5.9 Change Low Setpoint

The Low Setpoint value is typically above the 4 mA value for the sen-

sor. For example, if the 4 mA value is 50°F, the Low Setpoint might be

60°F. When the sensor crosses below this value, an alarm or event will

occur, depending on the sensor configuration.
The default Low Setpoint for each sensor is -950.0. Values that can be

entered range from:

• the 4 mA value + the Offset value (in the example, 50+5=55)

to

• the 20 mA value + the Offset value (in the example, 90+5=95)

To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 -

Change 20 mA Value and 9.5.6 - Change Offset Value.
To enter a new value:

• From the Setup Sensor Menu, choose Low Setpt for the selected

sensor and press Enter ↵ .

• To change the Low Setpoint:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.

9.5.10 Change High Setpoint

The High Setpoint value is typically below the 20 mA value for the sen-

sor. For example, if the 20 mA value is 90°F, the High Setpoint might

be 85°F. When the sensor crosses above this value, an alarm or event

will occur, depending on the sensor configuration.
The default High Setpoint for each sensor is +950.0. Values that can be

entered range from:

• the 4 mA value + the Offset value (in the example, 50+5=55)

to

• the 20 mA value + the Offset value (in the example, 90+5=95)

To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 -

Change 20 mA Value and 9.5.6 - Change Offset Value.
To enter a new value:

• From the Setup Sensor Menu, choose High Setpt for the selected

sensor and press Enter ↵ .

• To change the High Setpoint:

• Use the arrows

↑ ↓

to

choose a character.

• Press Enter ↵ to advance to the next character position.
• When finished, press Enter ↵ again.

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED : Y
LABEL: ROOM_TMP

↑ ↓=NEXT

=SELECT

UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N

> LOW SETPT: +0055.0

HIGH SETPT: +0999.9
SENSOR DELAY: 00:01

Change Low Setpoint

CHANGE LOW SETPOINT

LOW SETPT: +0060.0

↑ ↓=SELECT

=NEXT/END

Setup Sensor Menu

SETUP SENSOR_1

CONNECTED : Y
LABEL: ROOM_TMP

↑ ↓=NEXT

=SELECT

UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET:

+005.0

ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0060.0

> HIGH SETPT: +0095.0

SENSOR DELAY: 00:01

Change High Setpoint

CHANGE HIGH SETPOINT

HIGH SETPT: +0085.0

↑ ↓=SELECT

=NEXT/END