9.8.2 Modem Setup - Additional Features (Service Terminal Interface only)

The Service Terminal Interface offers four additional options for the modem that are not available

through the LCD interface:

• Enter Universal Monitor phone number
• Enable modem diagnostic messages
• Change modem dial prefix
• Change modem hang up delay after a call

To access these options:

• Connect to the Universal Monitor either from a remote computer or through the RS232 port (see

A.2 - Connecting to the Service Terminal Interface).

• At the Main Menu, enter 0 (zero—Setup System-Login Required).
• At the Login Menu, enter your password.
• At the Setup Menu, enter 6 (Setup Modem&Pagers).
• At the Setup Modem & Pagers menu, shown below, enter 5 to begin configuration.

• At the Change Modem Initialization String prompt, you may press Enter to bypass this option (or

see 9.8.1 - Modem Setup - Initialization String for instructions on entering the string).

Enter Universal Monitor Phone Number
This entry allows you to store the phone number that must be dialed to access the Universal Monitor

for future reference. This has no effect on the Universal Monitor’s modem settings or functionality—it

simply places the phone number in an accessible location.

• At the Universal Monitor Phone Number prompt, enter the phone number for the Universal Mon-

itor. The current setting appears in brackets []—nothing has been entered in the following exam-

ple.

• Press Enter to proceed, or Escape to cancel the entry. If you make a change, a confirmation mes-

sage appears: “Command Successful.”

Setup Modem & Pagers - Modem Setup

(Service Terminal Interface only)

SETUP MODEM&PAGERS

Input pager and
modem information

Select pager or modem

CURRENT NUMBER

*******************

1=PAGER NUMBER 1

An "A" is required

2=PAGER NUMBER 2

as 1st character

3=PAGER NUMBER 3

for an alpha pager,

4=PAGER NUMBER 4

an "N" for a numeric

5=MODEM CONFIGURATION

pager, and an "M"

6=RETURN TO SETUP MENU

for a remote modem.

7=RETURN TO MAIN MENU

*******************

SELECT A NUMBER:5

>CHANGE MODEM INITIALIZATION STRING(40 CHARACTERS MAX).
>[ATS0=1]
>[
>COMMAND SUCCESSFUL

>ENTER UNIVERSAL MONITOR PHONE NUMBER(40 CHARACTERS MAX).
>[]
>[
>COMMAND SUCCESSFUL