Sidewall direct venting, Vent/air termination – sidewall, Model kit number vent size – Lochinvar Knight 80 - 285 User Manual

Page 17

Advertising
background image

Installation & Operation Manual

17

4

Sidewall direct venting

Vent/air termination – sidewall

Follow instructions below when determining
vent location to avoid possibility of severe
personal injury, death, or substantial
property damage.

A gas vent extending through an exterior wall
shall not terminate adjacent to a wall or
below building extensions such as eaves,
parapets, balconies, or decks. Failure to
comply could result in severe personal injury,
death, or substantial property damage.

Installation must comply with local
requirements and with the National Fuel Gas
Code, ANSI Z223.1 for U.S. installations or
CSA B149.1 for Canadian installations.

Determine location

Locate the vent/air terminations using the following guidelines:

1. The total length of piping for vent or air must not exceed the

limits given in the General Venting Section on page 15 of
this manual.

2.

You must consider the surroundings when terminating the
vent and air:
a.

Position the vent termination where vapors will
not damage nearby shrubs, plants or air
conditioning equipment or be objectionable.

b.

The flue products will form a noticeable plume as
they condense in cold air. Avoid areas where the
plume could obstruct window views.

c.

Prevailing winds could cause freezing of
condensate and water/ice buildup where flue
products impinge on building surfaces or plants.

d.

Avoid possibility of accidental contact of flue
products with people or pets.

e.

Do not locate the terminations where wind eddies
could affect performance or cause recirculation,
such as inside building corners, near adjacent
buildings or surfaces, window wells, stairwells,
alcoves, courtyards, or other recessed areas.

Do not exceed the maximum lengths of the
outside vent piping shown in FIG. 4-1B.
Excessive length exposed to the outside
could cause freezing of condensate in the
vent pipe, resulting in potential boiler
shutdown.

Figure 4-1B Alternate Sidewall Termination of Air and
Vent w/Field Supplied Fittings

ƽ WARNING

ƽ WARNING

NOTICE

ƽ WARNING

ƽ WARNING Do not connect any other appliance to the

vent pipe or multiple boilers to a common
vent pipe. Failure to comply could result in
severe personal injury, death, or substantial
property damage.

ƽ WARNING Sidewall vent and air inlet terminations

must terminate in the same pressure zone.

If using the alternate sidewall termination:

3. The air piping must terminate in a down-turned elbow as

shown in FIG. 4-1B. This arrangement avoids recirculation

of flue products into the combustion air stream.

4. The vent piping must terminate in an elbow pointed

outward or away from the air inlet, as shown in FIG. 4-1B.

f.

Do not terminate above any door or window.
Condensate can freeze, causing ice formations.

g.

Locate or guard vent to prevent condensate damage
to exterior finishes.

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

VENT / AIR

TERMINATION

GRADE OR

SNOW LINE

12"

MIN

12"

MIN

TO

OVER-

HANG

POSSIBLE ORIENTATIONS

Figure 4-1A Sidewall Termination of Air and Vent

Model

Kit Number

Vent Size

80 - 210

KIT30045

3 inch vent

285

KIT30046

4 inch vent

Table 4A Sidewall Vent Kits

Advertising