Installation & Operation Manual

8

The Knight boiler gas manifold and
controls met safe lighting and other
performance criteria when the boiler
underwent tests specified in ANSI Z21.13
– latest edition.

Failure to keep boiler area clear and free of
combustible materials, gasoline, and other
flammable liquids and vapors can result in
severe personal injury, death, or
substantial property damage.

Installation must comply with:

• Local, state, provincial, and national codes, laws,

regulations, and ordinances.

• National Fuel Gas Code, ANSI Z223.1 – latest edition.
• Standard for Controls and Safety Devices for

Automatically Fired Boilers, ANSI/ASME CSD-1, when
required.

• National Electrical Code.
• For Canada only: B149.1 Installation Code, CSA C22.1

Canadian Electrical Code Part 1 and any local codes.

Before locating the boiler, check:

1.

Check for nearby connection to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power

2.

Locate the appliance so that if water connections should
leak, water damage will not occur. When such locations
cannot be avoided, it is recommended that a suitable
drain pan, adequately drained, be installed under the
appliance. The pan must not restrict combustion air
flow. Under no circumstances is the manufacturer to be
held responsible for water damage in connection with
this appliance, or any of its components.

3.

Check area around the boiler. Remove any combustible
materials, gasoline and other flammable liquids.

4. The Knight boiler must be installed so that gas control

system components are protected from dripping or
spraying water or rain during operation or service.

5. If a new boiler will replace an existing boiler, check for

and correct system problems, such as:

• System leaks causing oxygen corrosion or heat

exchanger cracks from hard water deposits.

• Incorrectly-sized expansion tank.
• Lack of freeze protection in boiler water causing system

and boiler to freeze and leak.

ƽ WARNING

This appliance is certified as an indoor
appliance. Do not install the appliance
outdoors or locate where the appliance will
be exposed to freezing temperatures or to
temperatures that exceed 100°F.

Failure to install the appliance indoors
could result in severe personal injury,
death, or substantial property damage.

Provide clearances:

Clearances from combustible materials
1. Hot water pipes—at least 1" from combustible materials.
2. Vent pipe – at least 1" from combustible materials.
3. See FIG.’s 1-1 and 1-2 on page 9 for other clearance

minimums.

Clearances for service access
1.

See FIG.’s 1-1 and 1-2 on page 9 for recommended
service clearances. If you do not provide the minimum
clearances shown, it may not be possible to service the
boiler without removing it from the space.

Closet and alcove installations

This appliance requires a special venting
system. The vent connection to the
appliance must be made with the starter
CPVC pipe section provided with the
appliance. The field provided vent fittings
must be cemented to the CPVC pipe
section. Use only the vent materials,
primer and cement specified in this
manual to make the vent connections.
Failure to follow this warning could result
in fire, personal injury, or death.

For closet and alcove installations as
shown in FIG.’s 1-1 and 1-2, CPVC vent
material must be used inside the structure.
The ventilating air openings shown in
FIG.’s 1-1 and 1-2 are required for this
arrangement. Failure to follow this
warning could result in fire, personal
injury, or death.

ƽ WARNING

ƽ WARNING

NOTICE

ƽ WARNING

1

Determine boiler location

A closet is any room the boiler is installed in which is less than
67 cubic feet for KBN080 and KBN105 models, 86 cubic feet
for KBN150 models, 107 cubic feet for KBN210 models,
and 120 cubic feet for KBN285 models.

An alcove is any room which meets the criteria for a closet
with the exception that it does not have a door.

Example: Room dimensions = 4 feet long, 4 feet wide, and
9 foot ceiling = 4 x 4 x 9 = 144 cubic feet. This would be
considered a closet for a Knight Boiler.