The Partially Dedicated Installation

Defrost air port needs to be drawn from clean
area without combustion appliances. To avoid
backdrafting of combustion products, never
draw defrost air from a room with a naturally
aspirated appliance, i.e. furnace, hot water
heater, gas dryer, stove, fire place etc.

WARNING

FIVE PORT MODELS - Partially Dedicated Installation for Models RNC10/RNC20

Weatherhood arrangement - requires a minimum
of 6' (2m) separation and a minimum of 18" (460mm)
clearance above grade or anticipated snow level.

CAUTION

Stale air drawn from key areas of home

(bathroom, kitchen, laundry)

Fresh air supplied to return air duct of air handler

HRV must be balanced.

Refer to “Airflow Balancing” in this manual.

WARNING

FOUR PORT MODELS

DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN

(Stale air drawn from key areas of home)

Forced Air

Furnace

Outdoors

* Unit is normally balanced
on HIGH speed
with furnace blower ON.

EXHAUST AIR from various parts of home.
i.e. bathrooms (if required), kitchens (if required).

Cool Air

Return

NOTES:
1. Furnace blower is recommended to operate when HRV is on to provide good air distribution.
2. Weatherhood arrangement is for drawing purposes only. 6' (2 m) minimum separation required.

18" (460 mm) above grade minimum.

3. Due to the differences in pressure between the HRV and the equipment it is being connected to,

the HRV's airflow must be confirmed on site, using the balancing procedure found in
the installation manual.

4. The duct port configuration (Fresh Air from Outside, Stale Air to Outside, etc.) varies from model

to model. Check specifications for the duct configuration on your model.

Return Air

3' (1 m) min .

recommended

Air

Handler

Outdoors

High efficiency filter
or electronic air cleaner

Field-supplied
Balancing Damper
(optional)

Cool Air

Return

Return Air

3' (1 m) min .

recommended

Stale Air To Outside

Fresh Air From Outside

STALE AIR from various parts of home.

i.e. bathrooms (if required), kitchens (if required).

* Unit is normally balanced
on HIGH speed
with furnace blower ON.