Fresh air, Stale air – Lifebreath RNC120D User Manual

Page 26

Advertising
background image

26

AccuFlow Gauge Kit
1 - Accu-Flow Balancing Gauge
2 - Connection Hoses
4 - Rubber Fittings
1 - Instruction Page

Lifebreath Accu-Flow is designed to quickly and accurately balance the
airflows on units equipped
with balancing ports. Normally the HRV/ERV would be balanced on
high speed. If the HRV/ERV is connected to a forced air system, both
systems should be set to run at the highest operational speed when
balancing is performed.

Procedure:
Step 1

Remove balancing port covers.

Step 2

Insert rubber fittings into balancing ports on door. (Use light pressure until fitting is snug).

Step 3

Attach tubes to balancing gauge.

Step 4

Place gauge on metal door (gauge is equipped with a magnetic strip). Ensure gauge is level/plumb.

Step 5

Connect tubes to door ports as illustrated in step 5 (record readings).

Step 6

Connect tubes to door ports as illustrated in Step 6. (record readings).

Note: It is normal practice to lightly tap gauge if reading is non-responsive.

Step 7
Damper airflows as required.

Step 8
Repeat Steps 5 and 6 as required to confirm airflows

Step 5

Measuring Fresh Air Side (Always connect left side port
first).

1

0

2

0

3

0

4

0

7

0

6

0

7

0

8

0

9

0

1

0

0

0

1

0

2

0

3

0

4

0

7

0

6

0

7

0

8

0

9

0

1

0

0

0

Fresh Air

Step 6

Measuring Stale Air Side (Always connect left side port
first).

Air Flow Balancing using AccuFlow Gauge Part No. 99-170

Models RNC155 and RNC200 Only