Recirculating Damper Defrost (4 port models)
The recirculating damper defrost HRV has an electronically
controlled damper defrost mechanism. The defrost timer is
activated when the outside temperature drops below 27°F (-
3°C). A motor driven damper door mechanism closes off the
supply air from outside allowing the exhaust air to recirculate
through the unit. After the defrost period, the damper operates in
the opposite direction to reopen the fresh air port. Defrost cycle
repeats until the temperature again rises above 27°F (-3°C).

Damper Defrost (5 port models)
The damper defrost HRV has a fifth port for defrost. An
electronically controlled damper defrost mechanism activates
the defrost timer when the outside temperature drops below
27°F (-3°C). A motor driven damper door mechanism closes off
the supply air from outside allowing room air to enter through
the fifth port of the unit. After the defrost period, the damper
operates in the opposite direction to reopen the fresh air port.
Defrost cycle repeats until the temperature again rises above
27°F (-3°C).

Defrost Operation

Lengthening the run time may result in ice
buildup on the core.

CAUTION

Defrost Cycle DIP Switch Settings - Increasing the Run Time

Defrost DIP Switch Settings (located on the circuit board) can be
adjusted to increase the unit’s run (ventilation) time. The three
minute defrost time cannot change.

HS

REMOTE

DFR2

DFR3

ON

SW1

*Lengthening the run time may result in ice build-up on the core.

HS

REMOTE

DFR2

DFR3

ON

SW1

HS

REMOTE

DFR2

DFR3

ON

SW1

OFF

ON

OFF

ON

Factory Setting

3 minute defrost time

17 minute run time

Option 1*

3 minute defrost time

25 minute run time

Option 2*

3 minute defrost time

30 minute run time

FRESH AIR

FROM OUTSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

TO INSIDE

FILTERS

BLOWERS

RECIRCULATING

DEFROST

DAMPER

MOTOR

CORE

STALE AIR

FROM INSIDE

STALE AIR

TO OUTSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

FROM INSIDE

FRESH AIR

TO INSIDE

BLOWERS

DEFROST

DAMPER

DEFROST

PORT

FILTERS