Installation instructions, General, Warning – L.B. White Oval 80™ Radiant User Manual

Page 8: Fig. 4 fig. 3

Advertising
background image

1. Read all safety precautions and follow L.B. White

recommendations when installing this heater. If

during the installation of the heater, you suspect that

a part is damaged or defective, call a qualified

service agency for repair or replacement.

2. A qualified service agency must check the heater

upon installation and periodically. This shall consist

of the following:

-- Start up and shut down of the heaters to test for

proper operation.

-- Leak check all gas pipe joints and gas hose

connections.

-- Gas pressure checks.

-- Ensuring the heater is properly positioned away

from combustible materials.

3.

Inlet Air Requirements:

This heater requires clean, fresh air from a

normal, atmospheric pressure environment for

proper operation and combustion. Contact

L.B.White Company if you have any questions

regarding the installation of this heater.

Inlet air may be drawn from the attic or through

side walls under a protective eve. See Figs. 3 and

4.

-- All inlet air seams and joints must be sealed

-- Do not use any filters on the air inlet system

-- The air inlet system must be kept as straight

as possible. No more than 1 - 90º bend is

allowed.

-- Contact L.B.White Co. if you have any

questions regarding the installation

of the heater

Inlet air for combustion must not be drawn from:

Inside the confinement room.

An attic or location where negative pressure

(vacuum) affects the air draw of the heater’s

fan. Examples include, but are not limited to:

a. houses with attic soffit vent area smaller

than ridge cap vent area

b. heater air inlet located within 20 ft. of

building ventilation fans

c. locations where wind and/or the

elements can create a negative

pressure.

Drawing Inlet Air From Attic

Use L.B.White air inlet kit 24950:

Drawing Inlet Air Through Side Walls

4. The heater is approved for indoor use only

5. Heater installation must take into consideration

proper hanging height to allow for clearance of

catching machines, litter spreaders, and any other

equipment used.

6. Ensure the heater installation does not interfere with

water, gas, or electrical lines.

7. Position the gas hose to prevent any contact with the

tubes, heat relectors, and burner box.

Installation Instructions

8

GENERAL

FOR INLET RUNS UP TO 20 FT., USE SMOOTH 4 IN. ID PVC
FOR RUNS OVER 20 FT., USE 6 IN.ID. PVC

AIR INLET
USE INLET CAP,
24861 FOR 4 IN PVC
CAN ALSO USE
1/4 X 1/4 HARDWARE
CLOTH FOR EITHER

4 IN. OR 6 IN. PVC

INSTALL SUPPORTS EVERY 5 FT. TO
PREVENT INLET SAGGING

USE MINIMUM LENGTH OF 4 IN DIAMETER FLEX DUCT WHEN
CONNECTING 4 IN.PVC TO BURNER BOX.
AN ADAPTER CONNECTION FOR THE BURNER BOX TO THE 6 IN.PVC
MUST BE OBTAINED THROUGH LOCAL SOURCE.

AIR INLET

W

ALL

ROOF

SECURE INLET TO WALL

WARNING

Combustion Hazard

Provide a properly located and sized fresh air inlet

for the heater.

-- Refer to Inlet Air Requirements instructions.

Failure to provide a fresh air inlet can lead to:

-- Sooting causing building damage

-- High carbon monoxide levels, causing serious

injury or death to livestock and humans

-- Overheating of the first 10 ft. tube, causing

fires leading to building damage and injury to

livestock and humans.

-- Higher temperature differences over the length

of the tubes, causing problems in temperature

control and bird performance

FIG. 4

FIG. 3

CLAMPS

2 FT. RIGID TUBE

FLEX TUBE CUT TO LENGTH
-- DO NOT EXCEED 4 FT. MAX. LENGTH
-- DO NOT KINK

12 IN. MIN. FROM
INSIDE OF ROOF

ENSURE INLET CAP
IS UNBLOCKED BY
INSULATION

12 IN. MIN. ABOVE
INSULATION

CUT 4 1/4 in. HOLE THROUGH CEILING
ADJACENT TO JOIST. SPREAD

INSULATION AWAY AND FASTEN

CEILING FLANGE TO JOIST.

SMOOTH INLET TUBE, MAX. 2
FT. LENGTH, 4 IN. DIA.
(FIT OVER CEILING FLANGE)

INLET CENTER

30-40 IN. FROM

BURNER BOX

CUT TUBE 6 IN. SHORTER IF
CEILING FLANGE IS CLOSER THAN 30 IN. FROM BURNER BOX.
ADD ADDITIONAL LENGTH OF 4 IN. RIGID TUBE (NOT INCLUDED) IF
CEILING FLANGE IS 40 IN. OR MORE FROM BURNER BOX.

MINMIZE
HORIZONTAL
TRAVEL OF FLEX
DUCT,
14 IN. MINIMUM
18 IN. MAXIMUM