Electrical installation − EMS version

Devices in a power range of 0.75 ... 4 kW (3/PE AC 400 V)

Terminal assignment of the power connections

7

l

125

EDS84DPS424 EN 5.0

X21 − motor connection − device version E84DxH...

Pin

Connection

Description

Data

Type Han 10E, sockets

84DWTX0212

1

U

Motor phase U

Max. 4 mm

2

Max. output voltage: mains voltage
Max. permanent output current:
type−dependent

2

V

Motor phase W

3

W

Motor phase V

4

BD1

Motor holding brake

Max. 4 mm

2

9

BD2

Motor holding brake (reference
conductor)

5

+PTC

Motor temperature monitoring

Max. 4 mm

2

PTC thermistor (PTC) or thermal
contact (NC contact)

10

−PTC

6, 7, 8

n. c.

+

PE

PE conductor

Max. 4 mm

2

, above housing

(

Stop!

Damage of the devices
A defective motor holding brake or a short circuit on the X21 connection
(motor and built−on accessories) causes internal damage to the device.
Possible consequences:

ƒ

If a defective motor holding brake is connected, the replacement device is
also damaged immediately.

Protective measures:

ƒ

When devices are replaced due to malfunction of the brake control, ensure
that defect−free motor holding brakes are connected.

ƒ

Check whether the motor holding brake and the connecting cable are free
from defects.

ƒ

Replace or repair defective components.

)

Note!

In the Lenze setting, the temperature monitoring of the motor is activated! To
start motors without thermal detectors, the response of the motor
temperature monitoring must be deactivated (C00585). Alternatively, a wire
jumper between +PTC and −PTC can be used to simulate a normal
temperature.