Lenze 8400 protec Manual User Manual
Page 90
Electrical installation − HighLine/StateLine version
Devices in a power range of 0.75 ... 7.5 kW (3/PE AC 400 V)
Terminal assignment of the power connections
l
90
EDS84DPS424 EN 5.0
(
Stop!
Damage of the devices
A defective motor holding brake or a short circuit on the X21 connection
(motor and built−on accessories) causes internal damage to the device.
Possible consequences:
ƒ
If a defective motor holding brake is connected, the replacement device is
also damaged immediately.
Protective measures:
ƒ
When devices are replaced due to malfunction of the brake control, ensure
that defect−free motor holding brakes are connected.
ƒ
Check whether the motor holding brake and the connecting cable are free
from defects.
ƒ
Replace or repair defective components.
)
Note!
In the Lenze setting, the temperature monitoring of the motor is activated! To
start motors without thermal detectors, the response of the motor
temperature monitoring must be deactivated (C00585). Alternatively, a wire
jumper between +PTC and −PTC can be used to simulate a normal
temperature.