ClearCube R Series Pentium 4 User Manual

Page 80

Advertising
background image

70 • Cage and Blade Installation

ClearCube Product Manual and Installation Guide

4. Plug the Factory Default Jumper cable (provided with your Cage in the Cage

accessory kit) into the RS485 OUT port on the back of the primary Cage.

5. Plug the AC cable back into the Cage and wait at least 15 seconds.
6. Remove the Factory Default Jumper cable.
7. Reattach the Ethernet cable to the RS485 OUT port on the back of the primary

Cage, if one was previously connected.

8. Power the Blades back up in the primary Cage (if desired).
The RMC network controller is reset to the factory default settings, with an IP address of

192.168.1.251. Resetting the RMC to its factory defaults and connecting to it with a

laptop computer using a crossover cable is a helpful troubleshooting technique.

Advertising
This manual is related to the following products: