Schneider Electric 890USE17700 User Manual
Page 130
Data Exchange
130
890USE17700 April 2004
Node Assembly
The next eight contiguous registers (registers 45367 through 45374) indicate the
presence or absence of configured modules in locations on the island bus. This
information is stored in Flash memory. At start up, the actual locations of the
modules on the island are validated by comparing them to the configured locations
stored in memory. Each bit represents a module:
z
A value of 1 in a given bit indicates that the configured module is not present.
z
A value of 0 indicates that the correct module is present in its configured location,
or that the location has not been configured.
The first two registers, shown below, provide the 32 bits that represent the module
locations available in a typical island configuration. The remaining six registers
(45369 through 45374) are available to support the island’s expansion capabilities:
15 14 13 12 11 10 9 8
7 6 5 4 3 2 1 0
Register 45367
module in 1
module in 2
module in 3
module in 4
module in 5
module in 6
module in 7
module in 16
module in 8
module in 9
module in 10
module in 11
module in 12
module in 13
module in 14
module in 15
15 14 13 12 11 10 9 8
7 6 5 4 3 2 1 0
Register 45368
module in 17
module in 18
module in 19
module in 20
module in 21
module in 22
module in 23
module in 32
module in 24
module in 25
module in 26
module in 27
module in 28
module in 29
module in 30
module in 31