Advanced Configuration Features

166

890USE17700 April 2004

The Data Image

The 9999 contiguous registers in the Modbus data image start at register 40001.
The illustration below shows a graphical representation of the data image and how
it is subdivided into nine distinct blocks:

Block 1 output data process image (4096 registers available)

Block 2 fieldbus master-to-HMI output table (512 registers available)

Block 3 reserved (512 registers available)

Block 4 128-register block reserved for future read/write use

Block 5 54-register block reserved for future read/write use

Block 6 54-register block reserved for future read-only use

Block 7 35 predefined island bus status registers

Block 8 input data/status process image (4096 registers available)

Block 9 HMI-to-fieldbus master input table (512 registers available)

Each block has a fixed number of registers reserved for its use. Whether or not all
the registers reserved for that block are used in an application, the number of
registers allocated to that block remains constant. This permits you to know at all
times where to begin looking for the type of data of interest to you.
For example, to monitor the status of the I/O modules in the process image, look at
the data in block 8 beginning at register 45392.

44609

45120

512 registers

Block 3

40001

44096

4096 registers

Block 1

44097

44608

512 registers

Block 2

45121

45248

Block 4

128 registers

45249

45302

54 registers

Block 5

45356

54 registers

45303

45392

49487

4096 registers

Block 8

49488

49999

512 registers

Block 9

Block 6

45391

35 registers

45357

Block 7