Logic Power
Flow
The figure below shows how the NIM’s integrated power supply generates logic
power and sends it across the primary segment:
The figure below shows how the 24 VDC signal is distributed to an extension
segment across the island:
The logic power signal is terminated in the STB XBE 1000 module at the end of the
segment (EOS).
Island Bus Loads
The built-in power supply produces 1.2 A of current for the island bus. Individual
STB I/O modules generally draw a current load of between 50 and 90 mA. (Consult
the Advantys STB Hardware Components Reference Guide (890 USE 172 00) for a
particular module’s specifications.) If the current drawn by the I/O modules totals
more than 1.2 A, additional STB power supplies need to be installed to support the
load.