Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

kVARh: Q4 Ph A

Accumulated Q4 Reactive Energy Ph A

AI46

kWh

0

347/348

kVARh: Q4 Ph B

Accumulated Q4 Reactive Energy Ph B

AI47

kWh

0

349/350

kVARh: Q4 Ph C

Accumulated Q4 Reactive Energy Ph C

AI48

kWh

0

351/352

kVAh: Import Ph A

Accumulated Appar. Energy Import Ph A

AI49

kWh

0

353/354

kVAh: Import Ph B

Accumulated Appar. Energy Import Ph B

AI50

kWh

0

355/356

kVAh: Import Ph C

Accumulated Appar. Energy Import Ph C

AI51

kWh

0

357/358

kVAh: Export Ph A

Accumulated Appar. Energy Export Ph A

AI52

kWh

0

359/360

kVAh: Export Ph B

Accumulated Appar. Energy Export Ph B

AI53

kWh

0

361/362

kVAh: Export Ph C

Accumulated Appar. Energy Export Ph C

AI54

kWh

0

363/364

kW: Ph A

Instantaneous Real Power Phase A

AI55

kW

1

365/366

kW: Ph B

Instantaneous Real Power Phase B

AI56

kW

1

367/368

kW: Ph C

Instantaneous Real Power Phase C

AI57

kW

1

369/370

kVAR: Ph A

Instantaneous Reactive Power Phase A

AI58

kVAR

1

371/372

kVAR: Ph B

Instantaneous Reactive Power Phase B

AI59

kVAR

1

373/374

kVAR: Ph C

Instantaneous Reactive Power Phase C

AI60

kVAR

1

375/376

kVA: Ph A

Instantaneous Apparent Power Phase A

AI61

kVA

1

377/378

kVA: Ph B

Instantaneous Apparent Power Phase B

AI62

kVA

1

379/380

kVA: Ph C

Instantaneous Apparent Power Phase C

AI63

kVA

1

381/382

PF: Ph A

Instantaneous Power Factor Phase A

AI64

PF

0.01

383/384

PF: Ph B

Instantaneous Power Factor Phase B

AI65

PF

0.01

385/386

PF: Ph C

Instantaneous Power Factor Phase C

AI66

PF

0.01

387/388

Volts: Ph A-B

Instantaneous Voltage Phase A to Phase B AI67

Volts

5

389/390

Volts: Ph B-C

Instantaneous Voltage Phase B to Phase C AI68

Volts

5

391/392

Volts: Ph A-C

Instantaneous Voltage Phase A to Phase C AI69

Volts

5

393/394

Volts: Ph A-N

Instantaneous Voltage Phase A to Neutral AI70

Volts

5

395/396

Volts: Ph B-N

Instantaneous Voltage Phase B to Neutral AI71

Volts

5

397/398

Volts: Ph C-N

Instantaneous Voltage Phase C to Neutral AI72

Volts

5

399/400

Amps: Ph A

Instantaneous Current Phase A

AI73

Amps

5

401/402

Amps: Ph B

Instantaneous Current Phase B

AI74

Amps

5

403/404

Amps: Ph C

Instantaneous Current Phase C

AI75

Amps

5

405/406

Max_Power

Max Power

AI76

kW

0

135

Reserved_AI77

(Reserved AI77)

AI77

n/a

65535

136

Energy_Resets

Count of Energy_Resets

AI78

n/a

0

147

Reserved_AI79

Reserved_AI79

AI79

n/a

65535

148

Reserved_AI80

Reserved_AI80

AI80

n/a

65535

151

Power_Up_Count

Count of Power Up Cycles

AI81

n/a

0

152

Output_Config

Output Configuration

AI82

n/a

0

153

Alarm Error Bitmap

Bitmap of all alarm bits

AI83

n/a

0

146