Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

Peak Real Energy Demand

Largest value recorded

AI26

kW

1

309/310

The peak demand is the highest demand value (register 26)

that has occurred. This value is also displayed on LCD for MAX

kW when the comms board is present.

Present Reactive Energy Sub-

Interval

SubInterval value currently

accumulating

AI27

KVAR

1

311/312

Present kVAR Sub-Interval. This is the currently accumulating

Sub-Interval KVAR, which is constantly changing.

Present Reactive Energy Demand Most recent Demand Sub-

Interval

AI28

KVAR

1

313/314

Present kVAR. This is the present kVar, which is updated at

the end of every sub-interval. This value is the average of

the previous N sub-intervals, where N is the number of sub-

intervals (register 37).

Peak Reactive Energy Demand

Largest value recorded

AI29

KVAR

1

315/316

Peak kVar. The peak kVar is the highest kVar value (register 28)

that has occurred.

Count of KWh resets

# of times kWh accumulator

was reset

AI30

n/a

1

31

Count of KWh resets. The number of times the peak demand

(register 27) has been reset. This value rolls over from 65535

to zero.

Count of Peak Demand Resets

# of times Peak kW Demand

was reset

AI31

n/a

1

32

Count of Peak Demand Resets. The number of times the peak

demand (register 27) has been reset. This value rolls over

from 65535 to zero.

Count of Peak kVAR Resets

# of times Peak kVAR Demand

was reset

AI32

n/a

1

33

Count of Peak kVar Resets. The number of times the peak kVar

(register 30) has been reset. This value rolls over from 65535

to zero.

Count of Elapsed Sub Intervals

Sub-intervals filled in current

Block

AI33

n/a

1

34

Count of Elapsed Sub Intervals. This counts the number

of subintervals that have elapsed. Because the demand

(register 28) is updated every sub-interval, this register may

be read to determine if an identical value in register 28 is

actually the same demand

# of Readings in Present sub-

interval

updated every 200 mS

AI34

n/a

5000

35

Number readings in present sub-interval. This value indicates

the number of readings that are represented by the present

subinterval (register 25). This register acts as an unsigned

integer. Values larger than 32767 should not be “trusted”.

See below for explanation of sub-interval reading count

overflow. This register will increment every 200 ms (5 times

per Second).

System ID

15024=Basic, 15025=Enhanced AI35

n/a

0

38

System ID. This register reads as 15024 for the Basic Meter and

15025 for the Enhanced Model to help identify the meter.

CT Size

Primary Rating, in Amps

AI36

n/a

0

39

CT Size. This register reads as the CT size: 100, 300, etc.

CT Number

Qty of CTs configured

AI37

n/a

0

40

CT Number. The number of CTs that are connected, 1,2, or 3.

Count of Phase Losses.

# of times phase loss has

occurred

AI38

n/a

1

43

Count of Phase Losses. The number of times a phase loss has

occurred on any phase. This value rolls over from 65535 to

zero.