Installation guide, E8950 – Veris Industries E8950 Install User Manual

Page 28

Advertising
background image

TM

E8950

INSTALLATION GUIDE

ZL0105-0B

PAGE 28

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

H8163 Series Energy Meter with H8163-CB Modbus Communication Board

The H8163 Series has 54 data objects and operates at 9600 or 19200 baud. All Date/Time values (AI39-47 & AV5-7) for the H8163 are float representations of hexadecimal data
with two values packed into each word, one in the lower byte (LSB) and one in the upper byte (MSB). Convert these values externally.

Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

Analog_input objects: (Read-only)
kWh Energy: Total

Accumulated Real Energy

AI1

kWh

0

259/260

kW: Total

Total Instantaneous Real Power

AI2

kW

1

261/262

kVAR: Total

Total Instantaneous Reactive

Power

AI3

kVAR

1

263/264

KVA: Total

Total Instantaneous Apparent

Power

AI4

kVA

1

265/266

PF: Total

Total Instantaneous Power

Factor

AI5

PF

0.01

267/268

Volts: L-L Avg

Voltage L-L average of active

phases

AI6

Volts

5

269/270

Volts: L-N Avg

Voltage L-N average of active

phases

AI7

Volts

5

271/272

Amps: Avg

Current Avg of active phases

AI8

Amps

5

273/274

kW: Ph A

Instantaneous Real Power

Phase A

AI9

kW

1

275/276

kW: Ph B

Instantaneous Real Power

Phase B

AI10

kW

1

277/278

kW: Ph C

Instantaneous Real Power

Phase C

AI11

kW

1

279/280

PF: Ph A

Instantaneous Power Factor

Phase A

AI12

PF

0.01

281/282

PF: Ph B

Instantaneous Power Factor

Phase B

AI13

PF

0.01

283/284

PF: Ph C

Instantaneous Power Factor

Phase C

AI14

PF

0.01

285/286

Volts: Ph A-B

Instantaneous Voltage Phase A

to Phase B

AI15

Volts

5

287/288

Volts: Ph B-C

Instantaneous Voltage Phase B

to Phase C

AI16

Volts

5

289/290

Volts: Ph A-C

Instantaneous Voltage Phase A

to Phase C

AI17

Volts

5

291/292

Volts: Ph A-N

Instantaneous Voltage Phase A

to Neutral

AI18

Volts

5

293/294

Volts: Ph B-N

Instantaneous Voltage Phase B

to Neutral

AI19

Volts

5

295/296

Volts: Ph C-N

Instantaneous Voltage Phase C

to Neutral

AI20

Volts

5

297/298

Amps: Ph A

Instantaneous Current Phase A

AI21

Amps

5

299/300

Amps: Ph B

Instantaneous Current Phase B

AI22

Amps

5

301/302

Amps: Ph C

Instantaneous Current Phase C

AI23

Amps

5

303/304

Present Real Energy Sub-Interval SubInterval value currently

accumulating

AI24

kW

1

305/306

Present Demand Sub-Interval. This is the currently

accumulating Sub-Interval demand, which is constantly

changing.

Present Real Energy Demand

(kW)

Most recent kW Demand Sub-

Interval

AI25

kW

1

307/308

Present Demand (kW). This is the present demand, updated

at the end of every Sub-Interval. This value is the average of

the previous N subintervals, where N is the number of sub

intervals (register 37).

Advertising