Installation guide, Troubleshooting, China rohs compliance information (efup table) – Veris Industries E8950 Install User Manual

Page 9

Advertising
background image

TM

E8950

INSTALLATION GUIDE

ZL0105-0B

PAGE 9

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TROUBLESHOOTING

Problem

Solution

Modbus device is not discovered as expected.

Use the main screen of the E8950 GUI to confirm which meters have been discovered.
Verify that the Modbus device is a model specifically supported by the E8950 (see Appendix 1).
Verify that the meter is connected to a control power source and is operating normally.
Verify that the Modbus 2-wire RS-485 connection is correctly wired from the E8950 to all

other Modbus devices and that the chain is terminated at both ends with 120 Ω resistors (not

included).

Verify that the Modbus RTU baud is set to the same rate on all Modbus devices and that parity

on all devices is set to “none.”

Verify that the E8950 is powered and operating (the light green LED is on).
Verify that the E8950 is in Discovery mode.

CHINA ROHS COMPLIANCE INFORMATION (EFUP TABLE)

部件名称

产品中有毒有害物质或元素的名称及含量Substances

铅 (Pb) 汞 (Hg)

镉 (Cd)

六价铬 (Cr(VI))

多溴联苯(PBB)

多溴二苯醚(PBDE)

电子线路板

X

O

O

O

O

O

O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下.

X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.

Z000057-0A