E8950

INSTALLATION GUIDE

ZL0105-0B

PAGE 19

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

Num of Sub-Intrvl per

Dem Intrvl

1=most recent; n(2-6)=avg of last n

AV10

n/a

0

149

Number of Sub-Intervals per Demand Interval. Sets the

number of sub-intervals that make a single demand

interval. For block demand, set this to 1. Default is 1. When

Sub-Interval Length (in object AV11) is set to 0 (sync-to-

comms mode), the value of this object is ignored.

Sub-Interval Length 10 to 32767 seconds (0= Sync-to-

Comms)

AV11

Seconds

0

150

Sub-Interval Length in hundredths of a second. For sync-to-

comms mode, which allows manual triggering of demand

intervals and the logging of another Trend_Log record, set

this value to 0 and write 21211 to the reset register (object

AV1) each time the sub-interval must be externally reset.

Default is 90000 (15 minutes). This variable is tied directly

to the Log_Interval property of all three Trend_Log objects

(their value is always the same as this one). Changing any of

these four properties changes all of them.

E51C2 and E51C3 Bi-Directional Energy Meter, cont.