Control setup example 4: on/off control – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 23

Advertising
background image

23

IM 04L31A01-02E

Setting PID Parameters in Setting Mode

1.

From the operation display, click the

MENU key

to display the control setting menu.

2.

Press the

#4 soft key

(PID parameters).

3.

Press the

arrow keys

to move the cursor (blue) to the setup item box, press the

soft

key

of each value according to the following figure.

The numerical values such as the SP are entered using the pop-up window that
appears by pressing the

Input soft key

.

Select 1

Set to 100.0

Select Reverse

Select 1

Set to P=120.0%, I=20 s,
D=0 s
(No need to change the
settings if the initial PID
values are set for
Press+Flow)

4.

Press the

DISP/ENTER key

to confirm the settings.

Control Setup Example 4: ON/OFF Control

Object of Control and Description

SSR

CX2000

Electric
furnace

TC

1

2

3

4

5

6

7

8

9

10

26

27

28

29

30

21

22

23

24

25

16

17

18

19

20

11

12

13

14

15

DISP

/ENTER

LOOP1 PV

1

LOOP1 NC/NO

2

1

Loop 1 PV input terminal
of the control input terminal block

2

Loop 1 voltage relay contact
output terminal of the control
output terminal block

ON/OFF
control output

PV

• Loop number:

1

• Control direction:

Reverse

• Relay hysteresis

Setpoint: 10.0, activation position: center

• Input type:

TC K type

• Measurement span: 0 to 1200°C
• Output type:

ON/OFF control output

• Temperature setpoint: 700°C

Basic Control Settings

1.

Show the basic control setting menu.
See “Control Setup Example 1” for the steps to show the menu.

Examples of Control Setup Operation