Setting mode (control) #1 control input range, 2 control alarm – Yokogawa Data Acquisition with PID Control CX2000 User Manual
Page 51
51
IM 04L31A01-02E
Parameter
Value or Selections
Initial Value
#3 Tuning setting
Tuning setting > Loop number
Ext1 to Ext16
Ext1
Tuning setting > 01 to 21
On/Off
Off
Tuning setting > Item ID
SP, A1, A2, A3, A4, P, I, D, OH, OL, MR, H, DR,
ETC
DB, PO, or ETC
Tuning setting > Item name
Up to 6 alphanumeric characters
ETC
Tuning setting > Register address
30001 to 39999, 300001 to 365535,
40001
40001 to 49999, 400001 to 465535
Tuning setting > Decimal point
0 to 4
0
Tuning setting > Range lower
–30000 to 30000, span width: 30000
0
Tuning setting > Range upper
–30000 to 30000, span width: 30000
10
Setting mode (Control)
#1 Control input range
Parameter
Selectable Range or Selections
Initial Value
Input range > Loop number
1 to 6
1
Input range > Input type
PV1, PV2, RemoteSP, or PVrange
PV1
Input range > Mode
TC, RTD, Scale, or 1-5V
TC
Input range > Type
DCV, TC, or RTD
TC
Input range > Range
TC: R/S/B/K/E/J/T/N//W/L/U/PLATI/PR/WRe
K
RTD: PT/JPT
PT
DCV: 20mV, 60mV, 200mV, 2V, 6V, 20V, or 50V
6 V
Input range > Span lower-limit
Within the range of Range
–200.0
Input range > Span upper-limit
Within the range of Range
1370.0
Input range > PV range
–30000 to 30000
Lower: 0.0, Upper: 2000.0
Input range > PV switching Lower limit –30000 to 30000
0.0
Input range > PV switching Upper limit –30000 to 30000
2000.0
Input range > Scale
–30000 to 30000
Lower: 0.00, Upper: 200.00
Input range > Unit
Up to 6 alphanumeric characters
–
Input range > Square root
On/Off
Off
Input range > Low-cut
0.0% to 5.0%
1.0%
Input range > Bias
On/Off
Off
Selectable range when On: EUS (–100.0% to 100.0%) of
0.0%
the measurement span
Input range > Filter
On/Off
Off
1 s to 120 s
1 s
Input range > Ratio
On/Off
Off
Selectable range when On: 0.001 to 9.999
1.000
#2 Control alarm
Parameter
Selectable Range or Selections
Initial Value
Alarm > Loop number
1 to 6
1
Alarm > 1 to 4
On/Off
Off
Alarm > Type
PV-H (PV high-limit), PV-L (PV low-limit),
PV-High
Dev-H (deviation high-limit), Dev-L (deviation low-limit),
Dev-H&L (deviation high & low limit),
D-W-H&L (deviation within high & low limits),
SP-H (SP high-limit), SP-L (SP low-limit),
Out-H (Output high-limit), or Out-L (Output low-limit)
Alarm > Standby
On/Off
Off
Alarm > Relay output
On/Off
Off
Alarm > Number
DO001 to DO006, DO101 to DO106, DO201 to DO206,
DO001, DO101, DO201
RO001 to RO012, or SW001 to SW036
Alarm > SP number
1 to 8
1
Alarm > Alarm value1 to 4 PV high/low limits: EU (0 to 100%) of measurement span,
1370.0
SP high/low limits: EU (0 to 100%) of measurement span,
Deviation high/low limits: EUS (–100 to 100%) of measurement span,
Deviation high & low limit and
deviation within high & low limits: EUS (0 to 100%) of measurement
span, or Output high/low limit: –5.0 to 105.0%
List of Parameters